GENERAL DATA

3 GENERAL DATA

3.1 CAPACITY TABLES

3.1.1 Nominal capacity-performance tables

3.1.1.1 Considerations

The heating capacity tables show the capacity and performance data in integrated values (with defrost correction factor
included).
The nominal heating and cooling capacities are based on the EN 14511 standard: Piping length: 7.5 meters; Piping lift: 0 meters.
Keywords:
CAP: Nominal capacity (kW)
COP: Coefficient of performance
EER: Energy efficiency ratio
DB: Dry bulb; WB: Wet bulb (ºC)
OAT: Outdoor ambient temperature (ºC)
WIT: Water inlet temperature (ºC)
WOT: Water outlet temperature (ºC)

3.1.1.2 Capacity-performance data


YUTAKI S
Outdoor unit model
Indoor unit model
OAT
WIT / WOT
(DB/WB)
CAP (Nom./Max.)
30 / 35 ºC
COP (Nom.)
CAP (Nom./Max.)
7 / 6 ºC
40 / 45 ºC
COP (Nom.)
CAP (Nom./Max.)
47 / 55 ºC
COP (Nom.)
CAP (Nom./Max.)
2 / 1 ºC
30 / 35 ºC
COP (Nom.)
CAP (Nom./Max.)
30 / 35 ºC
COP (Nom.)
CAP (Nom./Max.)
-7 / -8 ºC
40 / 45 ºC
COP (Nom.)
CAP (Nom./Max.)
47 / 55 ºC
COP (Nom.)
OAT
WIT / WOT
(DB/WB)
CAP (Nom.)
12 / 7 ºC
EER (Nom.)
35 / -- ºC
CAP (Nom.)
23 / 18 ºC
EER (Nom.)
Blank data: To be informed later.
16
PMML0335A rev.1 - 04/2016
RAS-2
RAS-2.5
WHVNP
RWM-2.0
RWM-2.5
NE
-
Unit
kW
4.3/7.0
-
5.25
kW
4.3/6.2
-
3.90
kW
4.3/6.0
-
3.00
kW
3.5/5.5
-
4.10
kW
4.3/4.7
-
2.85
kW
4.3/4.6
-
2.45
kW
4.0/4.2
-
1.93
-
Unit
kW
3.8/4.9
-
3.12
kW
4.1/6.1
-
3.81
RAS-4
RAS-3
WH(V)
WHVNP
WHVNP
NPE
RWM-3.0
RWM-4.0
NE
NE
NE
Heating operation
6.0/9.0
7.5/11.0
11.0/15.2
4.80
4.55
5.00
6.0/9.0
7.5/10.0
11.0/14.1
3.59
3.50
3.98
6.0/8.0
7.5/9.2
11.0/13.5
2.89
2.57
3.00
4.5/7.0
5.5/8.9
9.5/12.8
3.65
3.53
3.61
5.3/5.7
5.8/6.7
9.7/10.6
2.60
2.57
2.74
5.0/5.5
6.0/6.4
10.0/10.0
2.25
2.25
2.45
4.6/5.0
5.0/5.5
8.7/9.7
1.82
1.60
1.78
Cooling operation
(Using cooling kit accessory)
5.0/5.8
6.0/7.0
7.2/11.8
3.15
2.75
3.30
5.5/7.4
6.0/8.5
10.4/15.0
3.81
3.81
4.50
RAS-5
RAS-6
RAS-8
WH(V)
WH(V)
WHNPE
NPE
NPE
RWM-5.0
RWM-6.0
RWM-8.0
NE
NE
NE
14.0/16.7
16.0/17.8
20.0/25.5
4.71
4.57
4.30
14.0/15.7
16.0/17.3
20.0/25.0
3.61
3.40
3.40
14.0/15.2
16.0/17.0
20.0/24.0
2.80
2.50
2.72
10.5/13.9
11.1/15.0
12.3/20.0
3.55
3.41
3.41
11.5/12.0
12.0/13.0
14.2/17.9
2.65
2.57
2.57
11.0/11.6
11.5/12.5
15.0/16.6
2.25
2.15
2.08
9.7/11.2
10.5/12.0
12.5/14.5
1.85
1.75
1.70
9.5/12.6
10.5/13.5
14.0/16.4
3.22
2.82
3.12
12.9/16.0
13.5/17.5
17.0/23.5
4.02
3.81
3.81
RAS-10
WHNPE
RWM-10.0
NE
24.0/32.0
4.29
24.0/32.0
3.30
24.0/32.0
2.65
13.0/20.7
3.31
16.5/21.0
2.46
16.5/18.5
1.74
15.5/17.3
1.50
17.5/20.6
2.81
20.0/27.0
3.61