Herunterladen Inhalt Inhalt Diese Seite drucken

Maintenance And Repair; Personnel Qualifications; Operator Responsibilities; Operating Fluid - Wilo EMU KS-Serie Einbau- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für EMU KS-Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
en
9

Maintenance and repair

9.1

Personnel qualifications

9.2

Operator responsibilities

9.3

Operating fluid

9.3.1
Oil types
9.3.2
Filling quantities
234
Maintenance and repair
DANGER
Danger due to fluids hazardous to health!
If the pump is used in fluids hazardous to health, decontaminate the pump after dis-
mantling and before carrying out any other work! There is a risk of fatal injury! Ob-
serve the specifications in the work regulations! The operator must make sure that
the personnel have received and read the work regulations!
NOTICE
Only use lifting equipment in a technically sound condition!
Only use lifting equipment in a technically sound condition for lifting, lowering and
transporting the pump. Ensure that the pump does not become jammed during lift-
ing and lowering. Do not exceed the max. permissible bearing capacity of the lifting
equipment!
▪ Always carry out maintenance tasks in a clean location with good lighting. It must be
possible to position the pump safely and secure it.
▪ Only carry out maintenance tasks mentioned in these installation and operating in-
structions.
▪ Wear the following protective equipment while performing maintenance tasks:
– Safety goggles
– Safety shoes
– Safety gloves
▪ Electrical work: A qualified electrician must carry out the electrical work.
▪ Maintenance tasks: The technician must be familiar with the use of operating fluids and
their disposal. In addition, the technician must have basic knowledge of mechanical en-
gineering.
▪ Provide the necessary protective equipment and make sure that the personnel wears it.
▪ Collect operating fluids in suitable tanks and dispose of properly.
▪ Dispose of protective clothing used in accordance with regulations.
▪ Use only original parts of the manufacturer. Use of parts other than the original parts
releases the manufacturer from any liability.
▪ Collect any leakage of fluid and operating fluid immediately and dispose of it according
to the locally applicable guidelines.
▪ Provide the tools required.
▪ If flammable solvents and cleaning agents are used, open flames, naked lights and
smoking are prohibited.
Biological white oil is added to the motor and the sealing chamber. The following oil
types are recommended when changing the oil:
▪ Aral Autin PL*
▪ Shell ONDINA 919
▪ Esso MARCOL 52* or 82*
▪ BP WHITEMORE WOM 14*
▪ Texaco Pharmaceutical 30* or 40*
All oil types marked with "*" are approved for use with foods in accordance with
"USDA-H1".
Type
KS 8, KS 9, KS 14
KS 12, KS 15
KS 20
KS 24
KS 37, KS 70
KS...Ex
Sealing chamber
200 ml (6.8 US.fl.oz.)
140 ml (4.7 US.fl.oz.)
400 ml (13.5 US.fl.oz.)
350 ml (11.8 US.fl.oz.)
1400 ml (47.3 US.fl.oz.)
550 ml (18.6 US.fl.oz.)
Motor
900 ml (30.4 US.fl.oz.)
820 ml (27.7 US.fl.oz.)
1300 ml (44 US.fl.oz.)
1350 ml (45.6 US.fl.oz.)
3000 ml (101.4 US.fl.oz.)
-
WILO SE 2018-05

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Emu ks ex-serie

Inhaltsverzeichnis