Manual/Auto
Signalbezeichnung
HeatingSettings.Cor_HS2PumpBAutoMode
HeatingSettings.Cor_HS3PumpAAutoMode
HeatingSettings.Cor_HS3PumpBAutoMode
HeatingSettings.Cor_HW1PumpAutoMode
HeatingSettings.Cor_HP1PumpAutoMode
HeatingSettings.Cor_FrequencerAutoMode
HeatingSettings.Cor_BoilerAutoMode
TimePro.TimeGroupStatusHS1
TimePro.TimeGroupStatusHS2
TimePro.TimeGroupStatusHS3
74/92
Typ Modbus-
BACnet Default-
Adresse
X,3 500
X,3 501
X,3 502
X,3 503
X,3 504
X,3 505
X,3 506
X,3 508
X,3 509
X,3 510
Beschreibung
Wert
2
Manual/Auto HS2 P1B:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto HS3 P1A:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto HS3 P1B:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto HWC1:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto HP1:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto Frequency con-
verter:
0 = Manual-Off
1 = Manual-On
2 = Auto
4
Manual/Auto boiler:
0 = Manual-Off
1 = Start 1
2 = Start 2
3 = Start 1 and Start 2
4 = Auto
4
Manual/Auto Comfort time
HS1
0 = Manual-Off
1 = Manual-On
2 = Forced Off
3 = Forced On
4 = Auto
4
Manual/Auto Comfort time
HS2
0 = Manual-Off
1 = Manual-On
2 = Forced Off
3 = Forced On
4 = Auto
4
Manual/Auto Comfort time
HS3
0 = Manual-Off
1 = Manual-On
2 = Forced Off
3 = Forced On
4 = Auto
flexotron800
P100013568