flexotron800
Signalbezeichnung
HeatingSettings.Cor_CS1Curve_X2
HeatingSettings.Cor_CS1Curve_X3
HeatingSettings.Cor_CS1Curve_X4
HeatingSettings.Cor_CS1Curve_X5
HeatingSettings.Cor_CS1Curve_X6
HeatingSettings.Cor_CS1Curve_X7
HeatingSettings.Cor_CS1Curve_X8
HeatingSettings.Cor_CS1Curve_Y1
HeatingSettings.Cor_CS1Curve_Y2
HeatingSettings.Cor_CS1Curve_Y3
HeatingSettings.Cor_CS1Curve_Y4
HeatingSettings.Cor_CS1Curve_Y5
HeatingSettings.Cor_CS1Curve_Y6
HeatingSettings.Cor_CS1Curve_Y7
P100013568
Typ Modbus-
BACnet
Adresse
I,3
540
I,3
541
I,3
542
I,3
543
I,3
544
I,3
545
I,3
546
I,3
547
I,3
548
I,3
549
I,3
550
I,3
551
I,3
552
I,3
553
Default-
Beschreibung
Wert
22 °C
Outdoor temp for second
curvepoint for outdoor compen-
sated setpoint CS1
24 °C
Outdoor temp for third curvepoint
for outdoor compensated set-
point CS1
26 °C
Outdoor temp for fourth
curvepoint for outdoor compen-
sated setpoint CS1
28 °C
Outdoor temp for fifth curvepoint
for outdoor compensated set-
point CS1
30 °C
Outdoor temp for sixth curvepoint
for outdoor compensated set-
point CS1
32 °C
Outdoor temp for seventh
curvepoint for outdoor compen-
sated setpoint CS1
34 °C
Outdoor temp for eighth
curvepoint for outdoor compen-
sated setpoint CS1
15 °C
Setpoint for first curvepoint for
outdoor compensated setpoint
CS1
14 °C
Setpoint for second curvepoint
for outdoor compensated set-
point CS1
13 °C
Setpoint for third curvepoint for
outdoor compensated setpoint
CS1
12 °C
Setpoint for fourth curvepoint for
outdoor compensated setpoint
CS1
12 °C
Setpoint for fifth curvepoint for
outdoor compensated setpoint
CS1
11 °C
Setpoint for sixth curvepoint for
outdoor compensated setpoint
CS1
10 °C
Setpoint for seventh curvepoint
for outdoor compensated set-
point CS1
Actual/Setpoint
31/92