Actual/Setpoint
Signalbezeichnung
HeatingSettings.Cor_HB1Exercise
HeatingSettings.Cor_HB2Exercise
HeatingSettings.Cor_HB3Exercise
HeatingSettings.Cor_HB4Exercise
HeatingSettings.Cor_HB1Reset
HeatingSettings.Cor_HB2Reset
HeatingSettings.Cor_HB3Reset
HeatingSettings.Cor_HB4Reset
HeatingSettings.Cor_HBAlternate
HeatingActual.Cor_HB1RunMode
HeatingActual.Cor_HB2RunMode
HeatingActual.Cor_HB3RunMode
HeatingActual.Cor_HB4RunMode
HeatingActual.Cor_HB1TotalRT
HeatingActual.Cor_HB2TotalRT
HeatingActual.Cor_HB3TotalRT
HeatingActual.Cor_HB4TotalRT
HeatingActual.Cor_HB1NoOfStarts
HeatingActual.Cor_HB2NoOfStarts
HeatingActual.Cor_HB3NoOfStarts
HeatingActual.Cor_HB4NoOfStarts
HeatingActual.Cor_HB1ReturnTemp_Output
24/92
Modbus-
Typ
Adresse BACnet
L,1
8
L,1
9
L,1
10
L,1
11
L,1
12
L,1
13
L,1
14
L,1
15
L,1
16
R,4 377
R,4 378
R,4 379
R,4 380
R,4 381
R,4 382
R,4 383
R,4 384
R,4 385
R,4 386
R,4 387
R,4 388
R,4 389
AV,
40389
Default-
Beschreibung
Wert
0
Activate exercise Boiler 1:
0 = Exercise off
1 = Exercise on
0
Activate exercise Boiler 2
0
Activate exercise Boiler 3
0
Activate exercise Boiler 4
0
Boiler 1 Reset:
Resets the total run time when
set to 1.
0
Boiler 2 Reset
0
Boiler 3 Reset
0
Boiler 4 Reset
0
Command to alternate Boilers.
Run mode HB1:
0 = Off
1 = On (normal effect)
2 = High effect
Run mode HB2
Run mode HB3
Run mode HB4
Total run time Boiler 1
Total run time Boiler 2
Total run time Boiler 3
Total run time Boiler 4
Total number of starts Boiler 1
Total number of starts Boiler 2
Total number of starts Boiler 3
Total number of starts Boiler 4
Controller output HB1 Return
temp valve (0-100%)
flexotron800