Actual/Setpoint
5.9
Extra circuit
Signalbezeichnung
HeatingActual.Cor_ExtCircSensor1
HeatingActual.Cor_ExtCircSensor2
HeatingActual.Cor_ExtCircPumpStart L,2
HeatingSettings.Cor_ExtCircHyst
5.10
Cooling system (CS1)
Signalbezeichnung
HeatingSettings.Cor_CS1_SetPoint
HeatingActual.Cor_CS1PID_Input
HeatingActual.Cor_CS1PID_SetP
HeatingActual.Cor_CS1RoomTemp
HeatingActual.Cor_CS1ReturnTemp
HeatingActual.Cor_CS1PID_Output
HeatingActual.Cor_CS1CV1
HeatingActual.Cor_RH
HeatingActual.Cor_CS1PumpAStart
HeatingActual.Cor_CS1PumpBStart
HeatingActual.Cor_CS1PumpARun
HeatingActual.Cor_CS1PumpBRun
HeatingSettings.Cor_CS1PumpDayLimit(0)
HeatingSettings.Cor_CS1PumpNightLimit(0) R,3 605
HeatingSettings.Cor_CS1ParallelTransfer
HeatingSettings.Cor_CS1Curve_X1
30/92
Modbus-
Typ
BACnet
Adresse
R,4
399
AV,
40399
R,4
400
AV,
40400
269
BV,
20269
R,3
734
AV,
30734
Typ Modbus-
BACnet
Adresse
R,3 606
AV,
30606
R,4 342
AV,
40342
R,4 343
AV,
40343
R,4 344
AV,
40344
R,4 345
AV,
40345
R,4 348
AV,
40348
R,4 349
R,4 357
AV,
40357
L,2 238
L,2 239
L,2 240
BV,
20240
L,2 241
BV,
20241
R,3 604
R,3 538
I,3
539
Default-
Beschreibung
Wert
Extra control circuit Sensor 1
Extra control circuit Sensor 2
Starting the Extra circuit pump
5
Start pump if S1 > S2 + Hyst. °C
Default-
Beschreibung
Wert
17
Setpoint CS1
Supply temperature CS1
Setpoint supply temperature CS1
dew point compensated
Room temperature CS1
Return temperature CS1
Controller output CS1 (0-100%)
Control signal CS1 CV (0-10 V)
Humidity
Start signal pump CS1 P1A
Start signal pump CS1 P1B
Is set if running pump CS1 P1A
Is set if running pump CS1 P1B
17°C
Outdoor temp for pump stop day
CS1
17°C
Outdoor temp for pump stop
night CS1
0 °C
Parallel adjustment of setpoint-
curve CS1
20 °C
Outdoor temp for first curvepoint
for outdoor compensated set-
point CS1
flexotron800
P100013568