Sauter flexotron800 V2 Benutzerhandbuch Seite 76

Vorschau ausblenden Andere Handbücher für flexotron800 V2:
Inhaltsverzeichnis

Werbung

Manual/Auto
Signalbezeichnung
HeatingSettings.Cor_HS2RetPID_ManSet
HeatingSettings.Cor_CS1PID_Select
HeatingSettings.Cor_CS1PID_ManSet
HeatingSettings.Cor_CS1PumpAAutoMode
HeatingSettings.Cor_CS1PumpBAutoMode
TimePro.TimeGroupStatusCS1
HeatingSettings.Cor_PowerLimitPID_Select
HeatingSettings.Cor_PowerLimitPID_ManSet
HeatingSettings.Cor_CS1CoolUnitAutoMode
HeatingSettings.Cor_HBPID_Select
HeatingSettings.Cor_HBPID_ManSet
HeatingSettings.Cor_HB1ReturnTemp_Select X,3 664
HeatingSettings.Cor_HB1ReturnTemp_Man-
Set
HeatingSettings.Cor_HB2ReturnTemp_Select X,3 666
HeatingSettings.Cor_HB2ReturnTemp_Man-
Set
HeatingSettings.Cor_HB3ReturnTemp_Select X,3 668
76/92
Modbus-
Typ
BACnet
Adresse
R,3 592
X,3 593
R,3 594
X,3 601
X,3 602
X,3 616
X,3 618
R,3 619
X,3 622
X,3 662
R,3 663
R,3 665
R,3 667
Default-
Beschreibung
Wert
0
HS2 Return temp. controller
output if Manual-On mode
2
Manual/Auto CS1:
0 = Manual-Off
1 = Manual-On
2 = Auto
0
CS1 Supply temp controller
output if Manual-On mode
2
Manual/Auto CS1 P1A:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto CS1 P1B:
0 = Manual-Off
1 = Manual-On
2 = Auto
4
Manual/Auto Comfort time
CS1
0 = Manual-Off
1 = Manual-On
2 = Forced Off
3 = Forced On
4 = Auto
2
Manual/Auto HS1 power limit.:
0 = Manual-Off
1 = Manual-On
2 = Auto
0
HS1 power limit controller
output if Manual-On mode
2
Manual/Auto CS1 Cool Unit:
0 = Manual-Off
1 = Manual-On
2 = Auto
2
Manual/Auto HB:
0 = Manual-Off
1 = Manual-On
2 = Auto
0
HB controller output if Manual-
On mode
2
Return temperature valve
HB1:
0 = Manual-Off
1 = Manual-On
2 = Auto
0
HB1 return valve output if
Manual-On mode
2
Return temperature valve
HB2:
(See list for HB1)
0
HB2 return valve output if
Manual-On mode
2
Return temperature valve
HB3:
(See list for HB1)
flexotron800