flexotron800
Signalbezeichnung
HeatingActual.Cor_HS2ReturnTemp
HeatingActual.Cor_HS2PumpARun
HeatingActual.Cor_HS2PumpBRun
HeatingActual.Cor_HS2PumpAStart
HeatingActual.Cor_HS2PumpBStart
HeatingActual.Cor_HS2CV1
HeatingActual.Cor_HS2RetPID_Output
HeatingActual.Cor_HS2PID_Output
HeatingSettings.Cor_HS2PumpDayLimit(0)
HeatingSettings.Cor_HS2PumpNightLimit(0) R,3 525
HeatingActual.Cor_HS2OptActualStartTime X,4 351
HeatingActual.Cor_HS2RetPID_Input
HeatingActual.Cor_HS2RetPID_Output
HeatingActual.Cor_HS2RetPID_SetP
5.4

Heating System 3 (HS3)

Signalbezeichnung
HeatingActual.Cor_HS3PID_Input
HeatingActual.Cor_HS3PID_SetP
HeatingSettings.Cor_HS3Curve_X1
HeatingSettings.Cor_HS3Curve_X2
HeatingSettings.Cor_HS3Curve_X3
HeatingSettings.Cor_HS3Curve_X4
P100013568
Modbus-
BAC-
Typ
net
Address
R,4 9
AV,
40009
L,2
13
BV,
20013
L,2
14
BV,
20014
L,2
105
L,2
106
R,4 154
R,4 347
AV,
40347
R,4 161
AV,
40161
R,3 522
R,4 411
AV,
40411
R,4 414
R,3 732
AV,
30732
Modbus-
BACnet Default-
Typ
Adresse
R,4
10
AV,
40010
R,4
11
AV,
40011
I,3
35
I,3
36
I,3
37
I,3
38
Default
Description
value
Return temperature HS2
Is set if running pump HS2 P1A
Is set if running pump HS2 P1B
Start signal pump HS2 P1A
Start signal pump HS2 P1B
Control signal HS2 CV (0-10 V)
Controller output HS2 Return temp.
(0-100%)
Controller output HS2 (0-100%)
17°C
Outdoor temp for pump stop day
HS2
17°C
Outdoor temp for pump stop night
HS2
Start Optimizer, Time until start HS2
Actual difference between HP and
HS2 return
Controller output HS2 Return temp.
(0-100%)
HS2 Max Delta-T HP/HS
Beschreibung
Wert
Supply temperature HS3
Outdoor compensated setpoint supply
temperature HS3
-20°C
Outdoortemp for first curvepoint for
outdoor compensated setpoint HS3
-15°C
Outdoortemp for second curvepoint for
outdoor compensated setpoint HS3
-10°C
Outdoortemp for third curvepoint for
outdoor compensated setpoint HS3
-5°C
Outdoortemp for fourth curvepoint for
outdoor compensated setpoint HS3
Actual/Setpoint