Actual/Setpoint
Signalbezeichnung
HeatingSettings.Cor_CS1Curve_Y8
HeatingSettings.Cor_CS1RoomSetP
HeatingActual.Cor_DewpointTemp_Output
5.11
Difference Pressure Control (DP)
Signalbezeichnung
HeatingActual.Cor_DP
HeatingSettings.Cor_DPSetpoint
HeatingActual.Cor_FrequencyStart
HeatingActual.Cor_DPCV1
HeatingActual.Cor_DPPID_Output
5.12
Wind speed
Signalbezeichnung
HeatingActual.Cor_Windspeed
HeatingSettings.Cor_WindScale
HeatingSettings.Cor_HS1WindComp
HeatingSettings.Cor_HS2WindComp
HeatingSettings.Cor_HS3WindComp
32/92
Typ Modbus-
BACnet
Adresse
I,3
554
I,3
555
R,4 415
Modbus-
Typ
BACnet
Adresse
R,4 19
R,3 60
L,2
111
R,4 158
R,4 165
AV,
40165
Modbus-
Typ
Adresse BACnet
R,4
20
R,3
61
R,3
62
R,3
63
R,3
64
Default-
Beschreibung
Wert
9 °C
Setpoint for eighth curvepoint for
outdoor compensated setpoint
CS1
21 °C
Setpoint room temperature CS1
Calculated dewpoint temp.
Default-
Beschreibung
Wert
Difference pressure (kPa)
50 kPa
Setpoint difference pressure
Start signal Frequencer
Control signal Frequncer (0-10 V)
Controller output Frequencer
(0-100%)
Default-
Beschreibung
Wert
Wind speed (m/s)
1m/s/V
Scale factor for wind speed meter
0°C/m/s Wind compensation HS1
0°C/m/s Wind compensation HS2
0°C/m/s Wind compensation HS3