Actual/Setpoint
Signalbezeichnung
HeatingSettings.Cor_HB4SD1
HeatingSettings.Cor_HB1SD2
HeatingSettings.Cor_HB2SD2
HeatingSettings.Cor_HB3SD2
HeatingSettings.Cor_HB4SD2
HeatingSettings.Cor_HB1OffsetSD2
HeatingSettings.Cor_HB2OffsetSD2
HeatingSettings.Cor_HB3OffsetSD2
HeatingSettings.Cor_HB4OffsetSD2
HeatingSettings.Cor_HB1VesselConf
HeatingSettings.Cor_HB2VesselConf
HeatingSettings.Cor_HB3VesselConf
HeatingSettings.Cor_HB4VesselConf
HeatingSettings.Cor_HBAlternateWDay
HeatingSettings.Cor_HBAlternateHour
HeatingSettings.Cor_HBPumpStartDelay
HeatingSettings.Cor_HBPumpStopDelay
HeatingSettings.Cor_HBPumpExerciseHour
26/92
Modbus-
Typ
Adresse BACnet
R,3 647
AV,
30647
R,3 648
AV,
30648
R,3 649
AV,
30649
R,3 650
AV,
30650
R,3 651
AV,
30651
R,3 652
AV,
30652
R,3 653
AV,
30653
R,3 654
AV,
30654
R,3 655
AV,
30655
X,3
658
X,3
659
X,3
660
X,3
661
X,3
672
X,3
673
X,3
674
X,3
675
X,3
676
Default-
Beschreibung
Wert
5
HB4 Switch Difference 1
5
HB1 Switch Difference 2
5
HB2 Switch Difference 2
5
HB3 Switch Difference 2
5
HB4 Switch Difference 2
3
HB1 Offset Switch Diff. 2
3
HB2 Offset Switch Diff. 2
3
HB3 Offset Switch Diff. 2
3
HB4 Offset Switch Diff. 2
1
Vessel configuration HB1
0 = Off
1 = Off/On
2 = Off/Low/High
3 = Modulation
1
Vessel configuration HB2
(See list for vessel configuration
HB1)
1
Vessel configuration HB3
(See list for vessel configuration
HB1)
1
Vessel configuration HB4
(See list for vessel configuration
HB1)
0
Weekday for Boiler alternation
0 = No alternation
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
8 = Every day
10
Hour for Boiler alternation
30
Pump running time before it's
OK to start Boiler
30
Pump running time after Boiler
stop
15
Boiler pump Exercise hour
flexotron800
P100013568