Actual/Setpoint
5.3

Heating System 2 (HS2)

Signalbezeichnung
HeatingActual.Cor_HS2PID_Input
HeatingActual.Cor_HS2PID_SetP
HeatingSettings.Cor_HS2Curve_X1
HeatingSettings.Cor_HS2Curve_X2
HeatingSettings.Cor_HS2Curve_X3
HeatingSettings.Cor_HS2Curve_X4
HeatingSettings.Cor_HS2Curve_X5
HeatingSettings.Cor_HS2Curve_X6
HeatingSettings.Cor_HS2Curve_X7
HeatingSettings.Cor_HS2Curve_X8
HeatingSettings.Cor_HS2Curve_Y1
HeatingSettings.Cor_HS2Curve_Y2
HeatingSettings.Cor_HS2Curve_Y3
HeatingSettings.Cor_HS2Curve_Y4
HeatingSettings.Cor_HS2Curve_Y5
HeatingSettings.Cor_HS2Curve_Y6
HeatingSettings.Cor_HS2Curve_Y7
HeatingSettings.Cor_HS2Curve_Y8
HeatingSettings.Cor_HS2ParallelTransfer
HeatingActual.Cor_HS2RoomTemp
HeatingSettings.Cor_HS2RoomSetP
18/92
Modbus-
BAC-
Typ
net
Address
R,4 6
AV,
40006
R,4 7
AV,
40007
I,3
18
I,3
19
I,3
20
I,3
21
I,3
22
I,3
23
I,3
24
I,3
25
I,3
26
AV,
30026
I,3
27
AV,
30027
I,3
28
AV,
30028
I,3
29
AV,
30029
I,3
30
AV,
30030
I,3
31
AV,
30031
I,3
32
AV,
30032
I,3
33
AV,
30033
R,3 536
R,4 8
AV,
40008
R,3 34
AV,
30034
Default
Description
value
Supply temperature HS2
Outdoor compensated setpoint
supply temperature HS2
-20°C
Outdoortemp for first curvepoint for
outdoor compensated setpoint HS2
-15°C
Outdoortemp for second curvepoint
for outdoor compensated setpoint
HS2
-10°C
Outdoortemp for third curvepoint for
outdoor compensated setpoint HS2
-5°C
Outdoortemp for fourth curvepoint
for outdoor compensated setpoint
HS2
0°C
Outdoortemp for fifth curvepoint for
outdoor compensated setpoint HS2
5°C
Outdoortemp for sixth curvepoint for
outdoor compensated setpoint HS2
10°C
Outdoortemp for seventh curvepoint
for outdoor compensated setpoint
HS2
15°C
Outdoortemp for eighth curvepoint
for outdoor compensated setpoint
HS2
67°C
Setpoint for first curvepoint for out-
door compensated setpoint HS2
63°C
Setpoint for second curvepoint for
outdoor compensated setpoint HS2
59°C
Setpoint for third curvepoint for out-
door compensated setpoint HS2
55°C
Setpoint for fourth curvepoint for
outdoor compensated setpoint HS2
53°C
Setpoint for fifth curvepoint for out-
door compensated setpoint HS2
43°C
Setpoint for sixth curvepoint for out-
door compensated setpoint HS2
35°C
Setpoint for seventh curvepoint for
outdoor compensated setpoint HS2
25°C
Setpoint for eighth curvepoint for
outdoor compensated setpoint HS2
0 °C
Parallel transfer of setpointcurve
HS2
Room temperature HS2
21°C
Setpoint room temperature HS2