Communications via PROFIBUS PA: Pointek CLS 200
digital model
Notes:
• The following instructions assume that the user is familiar with PROFIBUS PA.
• For more detail, please see the full manual.
Pointek CLS 200 is a Class B, Profile Version 3.0, PA device. It supports Class 1 Master for cyclic
data exchange, and Class 2 for acyclic services.
To configure Pointek CLS 200 we recommend SIMATIC Process Device Manager (PDM) by
Siemens. (For more information go to > www.fielddevices.com: > Products and Solutions >
Products and Systems > Process Device Manager.)

Device Description

To use PDM with PROFIBUS PA, you will need the Device Description (DD) for Pointek CLS 200.
Go to > Device Catalog > Sensors/Level/Capacitive/Siemens Milltronics, or download it from:
www.siemens.com/milltronics under Downloads on the Pointek CLS 200 product page. After
downloading the DD file, you need to execute DeviceInstall.
Configuration
To configure a Profibus Class 1 Master (for example, a PLC), you will need the GSD file,
SIEM80E9.GSD. It can be downloaded from the Pointek CLS 200 product page at:
www.siemens.com/milltronics, under Downloads.

Setting the PROFIBUS address

The factory setting for the PROFIBUS address is 126. Reset it locally using Mode 15 (see page 13),
or remotely via the bus, using a parameterization tool such as SIMATIC PDM or HW-Konfig.
When cyclic data transfer with a Class 1 Master is in process, the address can only be
changed via the bus.

Bus Termination

Note: PROFIBUS PA MUST be terminated at both extreme ends of the cable for it to work
properly. Please refer to the PROFIBUS PA User and Installation Guidelines (order number
2.092), available from www.profibus.com.
Transmission of user data via PROFIBUS PA
The user data is the OUT parameter of the discrete input function block and is composed of the
Logical Level and Status bytes.
Page EN-16
Pointek CLS 200 ([PROFIBUS PA) – QUICK START MANUAL
7ML19985QE81