Error Codes; Spare Parts; Decommissioning/Disposal; Decommissioning - Wilo Control EC-Fire Einbau- Und Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English

10.4 Error codes

Code
Fault description
E006
Rotating field error
E022.x
Insulation fault
E040
Pressure/volume flow
sensor fault
E062
Water shortage
E080.x
Pump fault
E090
Plausibility error
".x" = info on the relevant pump to which the
error shown refers!
If the fault cannot be remedied, please contact
your nearest Wilo customer service point or rep-
resentative.

11 Spare parts

Spare parts or repairs may be ordered from local
specialist retailers and/or Wilo customer service.
To avoid queries and incorrect orders, all data from
the rating plate must be specified with
every order.
Subject to change without prior notice!

12 Decommissioning/disposal

12.1 Decommissioning

• All work must be carried out with the greatest
care.
• Proper protective clothing is to be worn.
• When working in enclosed spaces, a second per-
son must be present for safety reasons.
12.1.1 Deactivating automatic mode on the unit
1. Select menu item 3.01
2. Select "OFF"
12.1.2 Temporary decommissioning
For temporary deactivation, the control is
switched off and the switchgear is switched off via
the main switch.
The switchgear and the unit are now ready for
operation at any time. The defined settings are
stored retentively in the switchgear and are not
discarded.
60
Causes
Mains connection faulty, incorrect
rotating field
The insulation monitoring device
has been triggered
Sensor defective
No electrical connection to the
sensor
Protection against low water level
has triggered
Motor protection relay has tripped
(excess current or short-circuit in
the supply line)
Minimum current monitoring has
triggered
No volume flow within 10s after
pump start detected
12.1.3 Final shutdown
Remedy
Have the mains connection checked and
set a clockwise rotating field
Check pump, wiring, earth connection
Replace sensor
Repair the electrical connection
Check inlet/break tank; pumps restart
automatically
Check the pump (in accordance with the
installation and user manual for the pump)
and the supply line
Check the pump (in accordance with the
installation and user manual for the pump)
and the supply line
Check pump for correct delivery function
Check that the flow switch/flow sensor is
working correctly
Make sure that the ambient conditions are
observed accordingly:
• Ambient/operating temperature: 0 ... +40 °C
• Humidity: max. 90 %, non-condensing.
CAUTION! Beware of moisture!
The ingress of moisture will result in damage
to the switchgear. During standstill periods, pay
attention to the permissible humidity and
ensure the switchgear is stored so that it is
overflow-proof.
Switch off the switchgear using the main switch
("OFF" position).
RISK OF FATAL INJURY due to dangerous elec-
trical voltage!
Incorrect procedures can cause fatal electric
shocks.
This work may only be carried out by a qualified
electrician in accordance with locally applicable
regulations!
1. Switch off the switchgear using the main
switch ("OFF" position).
2. Switch off the entire unit so that it is voltage-
free and secure it against accidental activa-
tion.
3. If the terminals for SBM, SSM, EBM and ESM are
occupied, the external voltage source present
there must also be switched to a voltage-free
state.
4. Disconnect all power supply cables and pull
these out of the threaded cable connections.
5. Connect the ends of the power supply cables
so that no moisture can enter into the cable.
6. Remove the switchgear by undoing the screws
on the fire-extinguishing system/building
structure.