Output for an external signalling unit
Depending on the application of the switchgear,
the parameters of a 24 V (DC) output for an exter-
nal signalling device can be set as follows
(menu 5.67):
• "off": deactivated – no warning function
• "Error": the output is activated when a fault occurs
in the system
• "Run": the output is activated when at least one
pump is running
Fieldbus connection
The switchgear is prepared for connection via
ModBus RTU as standard. Connection is estab-
lished via an RS485 interface (electrical connec-
tion as per section 7.2.12).
The switchgear works as a Modbus slave. Basic
settings are made in menus 2.01 to 2.05.
Different parameters can be read and also
changed to some extent via the Modbus interface.
An overview of individual parameters and a
description of the data types used are shown in
the appendix.

6.2.2 Operation of the switchgear

Operating elements
• Main switch on/off (lockable in "off" position)
• The menu is controlled via the operating button:
• Turn: selection and set values
• Press: change menu level or confirm value
Fig. 17: Operation
• The LCD display shows the operating statuses of
the pumps and the controller.
Fig. 18: Appearance of display with pressure
switch
1
2
3
Installation and operating instructions Wilo-Control EC-Fire
1
Current pump status: number of registered
pumps; pump on/pump off
2
The device is in fieldbus mode
3
Indicator of the volume flow (0 = volume flow is
less than the zero-flow cut-off; 1 = volume flow
is greater than the zero-flow cut-off)
4
Switching status of the pressure switch
(0 = contact open; 1 = contact closed)
5
Indicator of the operating mode
(here always: p-c)
6
Standby pump activated; basic state of EC-Fire
Fig. 19: Appearance of display with pressure
sensor
1
3
1
Current pump status: number of registered
pumps; pump on/pump off
3
Indicator of the volume flow (0 = volume flow is
less than the zero-flow cut-off; 1 = volume flow
is greater than the zero-flow cut-off)
4
Current system pressure
5
Indicator of the operating mode
(here always: p-c)
6
Standby pump activated; basic state of EC-Fire
NOTICE
The display backlight is switched off if there is no
operation for 6 minutes.
If the red fault LED lights up or flashes immedi-
6
ately after activation, observe the error code
information on the display!
5
You can find an overview of all symbols in the
appendix.
4
English
6
5
4
45