8.2.9

Control unit for double system (up to model year 12/09)

Description of the display and control elements
Display elements (LEDs)
Normal mode
(for information
for the operator)
Problem
(for information for the
fitter, motor protection
switch also for the operator)
Control elements
Manual - 0 - Auto (pump 1)
Manual - 0 - Auto (pump 2)
Alarm reset
Motor protection switch 1
Motor protection switch 2
The operating elements can be accessed once the transparent housing cover has been removed. The housing
cover may be removed for operational purposes, but it only makes sense for service work.
The protective rating given is reduced when the cover is removed (water-tightness). Before removal, it must be
checked whether there is a hazard through high humidity or splashwater. In this case, the control unit must be
switched voltage-free first. In case of doubt, a qualified electrician must be consulted.
The current set at the motor protection switch must correspond with the rated current of the connected motor
Following operation, the housing cover must be sealed properly again to guarantee the protective rating
(water-tightness).
V 1.0
STANDARD CONTROL UNIT
operation
„Alarm" level
Level „on 2"
Level „on 1"
„Off" level
Pump 1
Pump 2
Phase / rotary field
Pump 2 MPS/temp
Pump 1 MPS/temp
Running time / level
Sliding switch
Sliding switch
Key
Switch
Switch
69/228
green Voltage supply OK
yel-
„Alarm" level reached
low
yel-
„On 2" level reached
low
yel-
„On 1" level reached
low
yel-
no function
low
green Pump output 1 activated
green Pump output 2 activated
red
Permanently lit: Phase failure (has display prio-
rity)
Flashing: Rotary field fault
red
Permanently lit: Motor protection switch pump 2
Flashing: Excessive motor temperature pump 2
red
Permanently lit: Motor protection switch pump 1
Flashing: Excessive motor temperature pump 1
red
Permanently lit: Running time fault
Flashing: Level fault
saving - priority treatment
Choice of operating mode for pump 1
Choice of operating mode for pump 2
Reset / alarm signal sensor test
Reset of a level fault display
Reset of excess motor temperature
Triggered when pump 1 has excess current
Triggered when pump 2 has excess current
has triggered
has triggered