Fault detection and elimination
Fault messages
1)
Keypad
PC
Error
12
Earth fault
OC2
a
13
Overload inverter
OC3
a
during
acceleration or
short circuit
14
Overload controller
OC4
a
during
deceleration
15
Controller overload
OC5
a
in stationary
operation
16
Motor overload
OC6
a
(I
50
Heatsink
OH
a
temperature
> +85 °C
Heatsink
OH
e
temperature
> +80 °C
53
PTC monitoring
OH3
a
(TRIP)
(is displayed if
C0119 = 1 or 4)
54
Controller
OH4
a
overtemperature
203
PTC monitoring
OH51
(is displayed if
C0119 = 2 or 5)
126
efesotomasyon.com - Lenze
Cause
Grounded motor phase
Excessive capacitive charging
current of the motor cable
Acceleration time too short
(C0012)
Defective motor cable
Interturn fault in the motor
Deceleration time set too short
(C0013)
Frequent and long overload
Motor is thermally overloaded,
2
x t overload)
for instance, because of
l
impermissible continuous
current
frequent or too long
l
acceleration processes
Ambient temperature too high Allow controller to cool and ensure
Heatsink very dirty
Impermissibly high currents or
too frequent and too long
acceleration
Motor too hot because of
excessive currents or frequent
and too long accelerations
PTC not connected
Controller too hot inside
Motor too hot because of
excessive currents or frequent
and too long accelerations
PTC not connected
EDK82MV371 DE/EN/FR 6.0
Remedy
Check motor, check motor cable
Use shorter motor cables with
lower charging current
Deactivate earth−fault detection for
testing purposes
l
Increase acceleration time
Check drive selection
l
Check wiring
Check motor
Increase deceleration time
l
Check size of external brake
l
resistor
Check drive selection
l
Check drive selection
Check setting of C0120
l
better ventilation
Clean heatsink
l
Check drive selection
Check load, if necessary,
l
replace defective bearings
Check drive selection
Connect PTC or switch off
monitoring
Reduce controller load
l
Improve cooling
l
Check fan in the controller
l
Check drive selection
Connect PTC or switch off
monitoring
L