Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze 8200 motec Montageanleitung Seite 115

Vorschau ausblenden Andere Handbücher für 8200 motec:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

efesotomasyon.com - Lenze
Code
No.
Name
C0007
Fixed
v
configuration of
digital inputs
uSEr
C0007
v
uSEr
(cont.)
L
The most important codes for commissioning
Possible settings
Lenze
Selection
0
E4
0
CW/CC
W
1
CW/CC
W
2
CW/CC
W
3
CW/CC
W
4
CW/CC
W
5
CW/CC
W
j6
CW/CC
W
7
CW/CC
W
8
CW/CC
W
9
CW/CC
W
10
CW/CC
W
E4
CW/CC
11
W
12
CW/CC
W
13
CW/CC
W
14
CCW/Q
SP
15
CCW/Q
SP
16
CCW/Q
SP
17
CCW/Q
SP
18
CCW/Q
SP
19
CCW/Q
SP
EDK82MV371 DE/EN/FR 6.0
Commissioning
E3
E2
E1
DCB
JOG2/3
JOG1/3
PAR
JOG2/3
JOG1/3
QSP
JOG2/3
JOG1/3
PAR
DCB
JOG1/3
QSP
PAR
JOG1/3
DCB
TRIP set
JOG1/3
PAR
TRIP set
JOG1/3
PAR
DCB
TRIP
set
QSP
PAR
TRIP
set
QSP
TRIP set
JOG1/3
TRIP
UP
DOWN
set
E3
E2
E1
DCB
UP
DOWN
PAR
UP
DOWN
QSP
UP
DOWN
CW/QS
DCB
JOG1/3
P
CW/QS
PAR
JOG1/3
P
CW/QS
JOG2/3
JOG1/3
P
CW/QS
PAR
DCB
P
CW/QS
PAR
TRIP
P
set
CW/QS
DCB
TRIP
P
set
7
IMPORTANT
Change under C0007 will
be copied to the
corresponding subcode of
C0410. Free configuration
under C0410 sets C0007 =
255!
l
CW/CCW = CW
rotation/CCW rotation
DCB = DC−injection brake
l
QSP = Quick stop
l
l
PAR = Parameter set
ó
changeover (PAR1
PAR2)
– PAR1 = LOW, PAR2 =
HIGH
– The terminal must be
assigned to the
function "PAR" in PAR1
and PAR2.
– Configurations with
"PAR" are only allowed
if C0988 = 0
TRIP set = external fault
l
l
Selection of
fixed setpoints
active
JOG1/3 JOG2/3
C0046
LOW
LOW
JOG1
HIGH
LOW
JOG2
LOW
HIGH
JOG3
HIGH
HIGH
113