Fault
Fault
Fault
Fault
Fault
Salt deficiency is displayed.
System supplies no soft or
blended water.
System supplies no soft water,
or flow rate too low
Salt deficiency lights up
although regeration material
has been filled.
Coloured rinsing water during
commissioning.
If the fault cannot be remedied with the aid of these instructions, our Factory Customer
If the fault cannot be remedied with the aid of these instructions, our Factory Customer
If the fault cannot be remedied with the aid of these instructions, our Factory Customer
If the fault cannot be remedied with the aid of these instructions, our Factory Customer
If the fault cannot be remedied with the aid of these instructions, our Factory Customer
Service must be consulted, giving the serial and production number (see nameplate on the
Service must be consulted, giving the serial and production number (see nameplate on the
Service must be consulted, giving the serial and production number (see nameplate on the
Service must be consulted, giving the serial and production number (see nameplate on the
Service must be consulted, giving the serial and production number (see nameplate on the
back of the system).
back of the system).
back of the system).
back of the system).
back of the system).
Cause
Cause
Cause
Cause
Cause
Too little regenerant in the
storage chamber (3 3 3 3 3 ).
No regenerant in the storage
chamber (3 3 3 3 3 ).
Power supply cut.
Adjusting spindle Blend
not set properly.
Primary pressure too low.
A hollow space has been
created around the contact
switch on the floor of the sieve.
Abrasion particles from the
exchanger resin.
Remedy
Remedy
Remedy
Remedy
Remedy
Replenish with regenerant and
press OK key until Salt
deficiency disappears.
Replenish with regenerant,
Press
OK
key
till
deficiency disappears. Wait 3
hours for brine to form and
trigger regeneration manually
for both exchanger columns in
succession.
Restore electricity connection.
Set according to Commis-
sioning section "Setting of
blended water hardness".
Raise primary pressure (if
necessar y,
set
pressure
reducer) and trigger Manual
regeneration.
Mix the regenerant in the brine
cabinet by hand.
Repeat Commissioning rinse.