14. Malfunctions

Faults are indicated by visual or acoustic messages (buzzer). In addition, the fault is reported by external messages to your smartphone /
tablet or PC by e-mail.
Causes for malfunctions include:
Reaching limit values (e.g. fi lling volumes reached)
Device malfunctions
Spent battery
Alarm text
Isolating valve
cannot be actuated!
Pressure sensor P1
does not report!
Pressure sensor P2
does not report!
Flow sensor
does not report!
Conductivity sensor LW1
does not report!
Conductivity sensor LW2
does not report!
Temperature sensor
does not report!
Number of fi lling cycles
exceeded. Clear alarm?
Suspected leakage:
Volume-based leakage.
Clear alarm?
Suspected leakage:
Time-based leakage.
Clear alarm?
Cartridge almost
exhausted
Cartridge is exhausted
Batteries spent
SL module
communication error
Insuffi cient inlet
pressure
Assembly, commissioning, operation and maintenance
Cause
The isolating valve cannot be actuated, possibly due to
dirt or a motor or limit switch defect.
Attention: Limited control of fi lling!
The pressure sensor P1 does not report any informa-
tion. Possibly due to a defect.
The pressure sensor P2 does not report any informa-
tion. Possibly due to a defect.
No turbine pulses were recorded over an extended
period of time, possibly due to dirt or a defect of the
turbine or the sensor.
Attention: Limited control of fi lling!
The conductivity sensor 1 for raw water hardness does
not report any information. Possibly due to a defect.
The conductivity sensor 2 for raw water hardness does
not report any information. Possibly due to a defect.
The temperature sensor does not report any informa-
tion. Possibly due to a defect.
The maximum number of admissible fi lling cycles has
been exceeded. Possibly due to a leakage which cau-
ses the system to refi ll too frequently.
The maximum admissible volume has been exceeded.
Possibly due to volume-based leakage.
The maximum admissible fi lling time has been excee-
ded. Possibly due to a time-based leakage.
The water conditioning cartridge is almost exhausted.
The water conditioning cartridge is exhausted.
The batteries are spent.
The SL module is not accessible.
The inlet line is shut off or the inlet pressure is insuf-
fi cient to refi ll the installation up to the desired target
value.
All-in-One+ Connect
Remedy
Please perform a functional check by manually
operating the isolating valve.
Please contact the SYR service.
Please contact the SYR service.
Open the water draw-off point and check whether the
control unit (LED) displays any turbine pulses.
Please contact the SYR service.
Please contact the SYR service.
Please contact the SYR service.
Please contact the SYR service.
Please eliminate the leakage or adjust the number of
fi lling cycles or the monitoring period. Press the but-
ton on the device for 3 seconds to open the isolating
valve. It is also possible to do so via the SYR App or in
the web application (http://syrconnect.de).
Check the heating installation for possible leakage
or other faults or adjust the fi lling volume. Press the
button on the device for 3 seconds to open the isola-
ting valve. It is also possible to do so via the SYR App
or in the web application (http://syrconnect.de).
Check the heating system for possible leakage or
other faults or adjust the fi lling or the refi lling time.
Press the button on the device to open the isolating
valve. It is also possible to do so via the SYR App or in
the web application (http://syrconnect.de).
Please replace the cartridge in good time.
Please replace the cartridge.
Please replace the batteries.
Please contact the SYR service.
The inlet pressure should be at least 1.5 bar higher
than the target pressure. Please check if all the iso-
lating valves upstream are open and the level of the
inlet pressure is suffi cient or contact the SYR service.