6.2.2. Assembly fl ange
•
First screw the connection plug as a connecting element into the fl ange up to the stop [image 1].
•
Mount the connection fl ange in the centre of the screwed bracket and use commercially available adapter pieces. Observe the fl ow
direction marked with arrows during assembly. Initially screw the fl ange only slightly to the wall bracket so that the distance can still
be varied [image 2].
[image 1]
•
When the fl ange is fi rmly mounted in the pipeline and the distance to the wall is determined, tighten the lock nut (SW 30).
6.2.3. Assembly of the All-in-One+ Connect
Mount the All-in-One+ Connect using the four hexagonal socket screws and both O-Rings to the connection fl ange.
Assembly, commissioning, operation and maintenance
[image 2]
Please respect the applicable standard DIN EN
12056 for the tundish connection of the backfl ow
preventer type BA to the waste water system.
All-in-One+ Connect
Please be sure to observe the
direction of fl ow indicated on
the casing by an arrow!