Anhang B
For 240 V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symme-
trical Amperes, 240 Volts Maximum, when Protected by Fuses, see Instruction Manual for
specified fuse details and alternate Branch Circuit Protection details."
For 480 V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symme-
trical Amperes, 480 Volts Maximum, when Protected by Fuses, see Instruction Manual for
specified fuse details and alternate Branch Circuit Protection details."
For all Models:
Branch Circuit Protection: input fusing for inverters of Drive Series F5-D and F6-D:
Inverter
model
F5/F6
07
07
09
09
10
10
12
12
13
14
*)The voltage rating of the Class rated fuses (CC,J or RK5) shall be at least equal to the
voltage rating of the Drives.
(#) manufactured by Siba Sicherungen-Bau GmbH
D - 42
Input
Voltage
Fuse class RK5 or J or CC
(V)
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
480 / 3ph
480 / 3ph
UL 248
[ A ] *
15
10
10
20
15
10
30
20
12
35
25
15
25
30
Semiconductor fuses
Cat. No.
(#)
50 140 06 40
50 140 06 20
50 140 06 12
50 140 06 40
50 140 06 25
50 140 06 12
50 140 06 63
50 140 06 35
50 140 06 16
50 140 06 100
50 140 06 50
50 140 06 25
50 140 06 40
50 140 06 40