Parameter Description
F3
Evaporator fan stop duration (while the evaporator fan
is stopped, the compressor can be turned on, the defrost
output will remain deactivated and the evaporator fan will
remain off )
F8
Differential of parameters F1, F16 and F17
F9
Evaporator fan shutdown delay after the compressor shut-
down (only if parameter F0 and/or parameter F2 are set to 2)
F11
Condenser temperature above which the condenser fan is
turned on (understood as "F11 + differential and provided
that the compressor is on); see also parameter F12
F12
Condenser fan shutdown delay after compressor shutdown
F15
Evaporator fan delay after door closure, that is after the de-
activation of the door switch input
F16
Evaporator temperature above which the evaporator fan
is turned off during pre-chilling, positive and negative
blast-chilling (only if parameter F0 is set to 1); see also pa-
rameter F8
F17
Cell temperature above which the evaporator fan is turned
off during pre-chilling, positive and negative blast-chilling
(only if parameter F0 is set to 1 or 2); see also parameter F8
i0
Effect caused by the opening of the door, that is the activa-
tion of the door switch input
0 = no effect
1 = the compressor and the evaporator fan will be turned
off and the cell light will be turned on, after the time set
through parameter i2 the display will show the code "id"
flashing and the buzzer will be activated (until the door is
closed); see also parameter F15
2 = the evaporator fan will be turned off and the cell light
will be turned on, after the time set through parameter i2
the display will show the code "id" flashing and the buzzer
will be activated (until the door is closed); see also param-
eter F15
i1
Type of contact of door switch input
0 = normally open (input active with contact closed)
1 = normally closed (input active with contact open)
i2
Door open alarm signal delay (code "id"); after the time set
through the parameter the compressor will be turned off
-1 = the alarm will not be reported
Default
2
2.0
0
15.0
30
15
20.0
90.0
Digital inputs
2
0
5
29
ENGLISH
Minimum
Maximum
value
value
0
15
0.1
15.0
0
240
0.0
99.0
0
240
0
240
-50.0
99.0
-50.0
99.0
0
2
0
1
-1
120
U.M.
min
°C/°F
s
°C/°F
s
s
°C/°F
°C/°F
---
---
min