12 Communication parameters
From menu 23, by entering the "modbus" submenu, it is possible to modify the following parameters relating to RS485_2:
Slave Address: from 1 to 254, default 1
Baud Rate: 9600/19200, default 19200
parity: NONE
13 Comands
Read Coil (Function Code = 01)
Read Holding Registers (Function Code = 03)
Read Input Register (Function Code = 04)
Write Multiple Coils (Function Code =15)
Write Multiple Holding Registers (Function Code = 16)
14 Parameter map
VARIABLE
ON/OFF
OPERATING SPEED
TEMPERATURE SETPOINT 1
(SP1) BYPASS
TEMPERATURE SETPOINT 2
(SP2) POSTHEATER
SPEED 1 SUPPLY (V1S)
SPEED' 2 SUPPLY (V2S)
SPEED' 3 SUPPLY (V3S)
SPEED' 4 SUPPLY (V4S)
(IF EXISTING)
SPEED' 1 EXHAUST (V1H)
SPEED' 2 EXHAUST (V2H)
SPEED' 3 EXHAUST (V3H)
SPEED' 4 EXHAUST (V4H)
ENABLING TIME BANDS
MINIMUM SPEED
ALLOWED (VMIN)
MAXIMUM SPEED
ALLOWED (VMAX)
RELATIVE HUMIDITY HR%
AIR QUALITY VOC
TEMPERATURE NTC 1 (INT)
TEMPERATURE NTC 2 (EST)
TEMPERATURE NTC 3 (EXH)
TEMPERATURE NTC 4 (SUP)
BYPASS ACTIVE
NOFROST ACTIVE
POSTHEATER ACTIVE
ALARM PRESENCE
*) The "alarm presence" variable returns a WORD variable (16 bits) in which each single bit signals the presence or absence
of an alarm, in the following sequence:
60
TYPE
PERMITS VALUES
BOOL
TRUE, FALSE
16BIT-INT
1,2,3,4
16BIT-INT
15 ÷ 30
16BIT-INT
10 ÷ 25
16BIT-INT
VMIN ÷ V2S
16BIT-INT
V1S ÷ V3S
16BIT-INT
V2S ÷ V4S
16BIT-INT
V3S ÷ VMAX
16BIT-INT
VMIN ÷ V2H
16BIT-INT
V1H ÷ V3H
16BIT-INT
V2H ÷ V4H
16BIT-INT
V3H ÷ VMAX
BOOL
TRUE, FALSE
16BIT-INT
0 ÷ VMAX
16BIT-INT
VMIN ÷ 100
16BIT-INT
0 ÷ 100
16BIT-INT
0 ÷ 100
16BIT-INT
-40 ÷ 60
16BIT-INT
-40 ÷ 60
16BIT-INT
-40 ÷ 60
16BIT-INT
-40 ÷ 60
BOOL
TRUE,FALSE
BOOL
TRUE,FALSE
BOOL
TRUE,FALSE
16BIT-INT
(*)
READ/WRITE
ADDRESS
W/R
16399
W/R
16400
W/R
W/R
16401
W/R
16402
W/R
16403
W/R
16404
W/R
16405
W/R
16406
W/R
16407
W/R
16408
W/R
16409
W/R
16410
R
16411
R
8961
R
8964
R
8974
R
8976
R
8977
R
8978
R
8979
R
8981
R
8982
R
8983
R
8984