6.6 Electrical connections
CAUTION: To connect the HMI remote display to the machine, use cables with a section between 0.35 mm2 and 2.5 mm2.
Max length 60 m. Given that the display connection cable should be kept separate or away from the power cables, if there
are problems of electromagnetic interference from other devices installed in the environment (which produce malfunction of
the display), it is recommended to use shielded cables.
CAUTION: To connect the product power supply, use a cable with a minimum section of 3X0.75 mm2 H05VV-F.
12
POWER SUPPLY
220-240V
~50-60Hz
PE
L
N
2
3
4
5
6
Wires color code
BK=black
BK=blue
BN=brown
GNYE=yellow
RD=red
WH=white
YE=yellow
40
1
220-240V
~50-60Hz
220-240V
~50/60Hz
VCC
A
B
GND
1.
Mains 2 poles switch
2.
Preheater (remote 220-240Vac ~50/60Hz relay coil)
3.
Postheater (remote 220-240Vac ~50/60Hz relay coil)
4.
Dry contact (remote switch/relay)
5.
Remote HMI
6.
Remote Modbus Master Unit
GNYE
BN
BU
BU
BN
BU
BN
POSTH