Tabelle 4 Output Command Structure - orbit controls OCM642 Betriebsanleitung

Präzisions - widerstandsdekade
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

OCM642 Programmierbare Widerstandsdekade
:OUTPut[:STATe]
Syntax:
:OUTPut[:STATe] <BOOL>
:OUTPut[:STATe]?
Description:
This command switches ON/OFF output terminals. This command operates in
conjunction with OUTP:SHOR command:
Parameters:
<BOOL>
·ON
·OFF
·1
·0
Remarks:
Overlapped command
Value is set to default after reset
Example:
OUTP ON
OUTP? Response: 1
:OUTPut:SWITching
Syntax:
:OUTPut:SWITching <CPD>
:OUTPut:SWITching?
Description:
If output amplitude is changed and output terminals are already switched on,
some glitches appear at output terminals. This setting allows selecting a method
how new resistance at output terminals is achieved.
Parameters:
<CPD>
·FAST
·SMOoth
·OPEN
·SHORt
Remarks:
Overlapped command
Value is not affected by reset
Example:
OUTP:SWIT FAST
OUTP:SWIT? Response: FAST
39
OUTP:STAT
OUTP:SHOR
OFF
OFF
ON
ON

Tabelle 4 OUTPut command structure

{ON|OFF|1|0} (default 0)
output terminals are switched on
output terminals are switched off
same as ON
same as OFF
{FAST|SMOoth|OPEN|SHORt} (default FAST)
new resistance is set as fast as possible
new resistance is set with minimal ouput changes
open function is activated before new resistance is set
short function is activated before new resistance is set
Output terminals
OFF
Open
ON
Open
OFF
Resistance
ON
Short
Orbit Controls AG