Error Message
Cause
Incorrect OP type
Incorrect target device
being addressed.
CPU not in STOP
CPU in target device is not
mode
in STOP mode.
Incorrect CPU type
Incorrect target device
being addressed.
Block too large
The CPU-specific
maximum block size has
been exceeded.
Not supported
Target device does not
support the requested
service.
Invalid SDB
The system data block
(SDB) is not valid on this
CPU or is defective.
CPU memory full
The maximum size of the
working memory (RAM) or
load memory of the CPU
has been exceeded.
36
Manual
Remedy
Check setting of target
device on the UD 700 and
in Protool.
Switch the operating mode
of the target device CPU to
STOP (key switch)
Check whether the UD 700
is connected to the correct
target device.
Check setting of the target
device on the UD 700.
Observe the restrictions for
the CPU in use.
Check the target device
type.
Observe the restrictions for
the CPU in use.
Check the target device
type.
Observe the restrictions for
the CPU in use.
Check the target device
type.
Check the target device
type.
Correct the user program.