Manual
Error Message
Cause
A timeout has occurred
while waiting for a
response.
Communication error
A timeout has occurred
while attempting to connect
to the MPI network.
Highest station address is
incorrect.
Transmission rate is
incorrect.
Error in MPI network.
Double MPI address
The MPI address set for the
UD 700 already exists in
the MPI network.
No active station
No active station in the
MPI network.
No more buffer
No buffer for temporary
memory.
OP error
OP reports general error.
Flash error on OP
Error while accessing flash
memory in OP.
OP flash is full
The flash memory in the
OP is full.
OP Protocol error
Protocol error caused by
OP.
Terminated by user
Terminated at OP by user
No SYNC frame
UD 700 and ProTool are
not synchronized.
Incorrect OP
Incorrect protocol.
protocol.
UD 700
C79000-Z7074-C123-01
UD 700
Remedy
Check the status of the
target device.
Adjust the HSA setting in
the UD 700 to match that of
the MPI network.
Check transmission rate of
all nodes in the MPI
network.
Check cable connection to
MPI network.
Set another, free MPI
address for the UD 700.
Check the cable connection
to the MPI network.
Check whether the target
device is switched on.
Check the status of the
target device.
Check the status of the
target device.
Check the status of the
target device.
Restrict configuration.
Check setting of target
device at the UD 700.
Restart download.
Check setting of target
device on the UD 700 and
in ProTool.
35