Herunterladen Inhalt Inhalt Diese Seite drucken

Hart-Command 15 : Read Primary Variable Output Information; Hart-Command 16 : Read Final Assembly Number; Hart-Command 17 : Write Message - ABB Industrial IT enable FXT4000 COPA-XT Schnittstellenbeschreibung

Inhaltsverzeichnis

Werbung

3.10 HART-Command 15 : Read Primary Variable Output Information

Request
none
Data Bytes
Response
Data Bytes
#3..#6
#7..#10
#11..#14
#15
#16
Response
Codes
Bemerkung

3.11 HART-Command 16 : Read Final Assembly Number

Request
none
Data Bytes
Response
#0..#2 Final Assembly Number
Data Bytes
Response
Codes

3.12 HART-Command 17 : Write Message

Request
#0..#23 Message, Packed-ASCII
Data Bytes
Response
#0..#23 Message, Packed-ASCII
Data Bytes
Response
Codes
12
#0
Alarm Select Code, Table VI
#1
Primary Variable Transfer Function Code, Table III
#2
Primary Variable Range Values Units Code, Table II
Primary Variable Upper Range Value, IEEE754
Primary Variable Lower Range Value, IEEE754, always Zero
Primary Variable Damping Value, IEEE754, Units of Seconds
Write Protect Code, Table VII
Private Label Distributor Code, Table VIII
0
No Command Specific Error
5
Incorrect Byte Count
Alarm Selection Code
PV Transfer Function Code
PV Upper Range Value
PV Lower Range Value
PV Damping Value
Write Protect Code
Private Label Distributor
0
No Command Specific Error
5
Incorrect Byte Count
0
No Command Specific Error
5
Incorrect Byte Count
= 0 = High, 1 = Low
= 0 = Linear
= QmaxDN
= 0
= Dämpfung
= 251 = Not Implemented
= 18 =ABB-FISCHER&PORTER
Revision
Revision
Revision

Werbung

Inhaltsverzeichnis
loading