4.6 HART-Command 44 : Write Primary Variable Units

Request
Data Bytes
Response
Data Bytes
Response
Codes

4.7 HART-Command 45 : Trim Primary Variable Current DAC Zero

Request
#0..#3 Externally Measured Primary Variable Current Level, IEEE 754, Units of mA
Data Bytes
Response
#0..#3 Actual Measured Primary Variable Current Level, IEEE 754, mA
Data Bytes
Response
Codes

4.8 HART-Command 46 : Trim Primary Variable Current DAC Gain

Request
#0..#3 Externally Measured Primary Variable Current Level, IEEE 754, Units of mA
Data Bytes
Response
#0..#3: Actual Measured Primary Variable Current Level, IEEE 754, mA
Data Bytes
Response
Codes
16
#0 Primary Variable Unit Code
#0 Primary Variable Unit Code
0
No Command Specific Error
2
Invalid Selection
5
Incorrect Byte Count
0
No Command Specific Error
3
Passed Parameter to Large (> 5mA)
4
Passed Parameter to Small (< 3mA)
5
Incorrect Byte Count
9
Not in Proper Current Mode
11
In Multidrop Mode
0
No Command Specific Error
3
Passed Parameter to Large (> 22mA)
4
Passed Parameter to Small (< 18mA)
5
Incorrect Byte Count
9
Not in Proper Current Mode
11
In Multidrop Mode