NOTE
Rating plate
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 40 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Altitude: 3000 m
Ambient temperature: 35 °C
→ Total derating = 0.845 x 1.125 = 0.95
Fig. 13-2
Rating plate
Operating Instructions
x Derating
altitude
ambient temperature
Technical Data
K
= 0.845
1
K
= 1.125
2
Unit designation
List of unit options
Year of manufacture
Month of manufacture
13-3