f, n, T control?
(P100 = 3, 4, 5)
no
yes
P115 = 4
Wait
P536 = ?
P115 = 5
Wait
Finished
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
Calculate motor model "No-load measurement"
NOTICE: Current flows through the motor and the rotor rotates!
After "P" key is pressed, the alarm message "A080" appears.
The converter must be switched on within 20 seconds!
Wait until the converter is "Ready for ON" again (°009)
For fault "Fxxx", refer to chapter "Faults and alarms"
Enter the dynamic performance of the speed control circuit
in %
Important for subsequent controller optimization.
Calculate motor model "Controller optimization"
NOTICE: Current flows through the motor, the rotor rotates!
After "P" is pressed, the alarm message "A080" appears.
The converter must be switched on within 20 seconds!
Wait until the converter is powered-down
(Operating status "Ready for ON" (°009))
For fault "Fxxx", see chapter "Faults and alarms"
Operating Instructions
Parameterizing Steps
9-59