04.2008
DC voltage 510 V to 650 V
Order
Rated
Number
direct
Cross-
current
section
6SE70...
VDE
[A]
[mm²]
16-1TA61
7.3
2.5
18-0TA61
9.5
2.5
21-0TA61 12.1
2.5
21-3TB61 15.7
4
21-8TB61 20.8
6
22-6TC61 30.4
10
23-4TC61 40.5
16
23-8TD61 44.6
16
24-7TD61 55.9
25
26-0TD61 70.2
35
27-2TD61 85.7
50
DC voltage 675 V to 810 V
Order
Rated
number
direct
Cross-
current
section
6SE70...
VDE
[A]
[mm²]
14-5UB61
5.4
2.5
16-2UB61
7.4
2.5
17-8UB61
9.3
2.5
21-1UB61 13.0
2.5
21-5UB61 18.0
4
22-2UC61 26.2
10
23-0UD61 34.5
10
23-4UD61 40.5
16
24-7UD61 55.4
25
NOTE
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
Infeed side
Recom-
Internal DC fuse
1)
mended fuse
AWG gR (SITOR)
Type
[A] 3NE...
14
25
8015
14
25
8015
14
25
8015
12
50
8017
10
50
8017
2)
8
80
8020
100A22F 700 100
2)
6
80
8020
100A22F 700 100
2)
6
125 8022
100A22F 700 100
2)
4
125 8022
100A22F 700 100
2)
2
160 8024
2)
1
160 8024
Infeed side
Recom-
Internal DC
1)
mended fuse
fuse
AWG GR (SITOR)
Type
[A] 3NE...
14
32
4101
14
32
4101
14
32
4101
14
32
4101
12
32
4101
8
50
4117
2)
8
80
4120
100A22F 700 100
2)
6
80
4120
100A22F 700 100
2)
2
100 4121
100A22F 700 100
Table 7-1
Conductor cross-sections, fuses
1) Applies to single-wire/stranded cables, see also Table 7-2 "Possible
connection cross-sections ".
2) Fuses aR (SITOR)
The connection cross-sections are determined for copper cables at
40 °C (104 °F) ambient temperature and cables with a permissible
operating temperature at the conductor of 70 °C (installation type C
(taking the bundling factor of 0.75 into account) in accordance with DIN
VDE 0298-4/08.03).
Additional fuses on the infeed side are not necessary for rated DC
voltages of 510 V to 810 V on account of the DC fuses integrated in the
unit, provided that the supply cables to the DC bus are laid in a short-
circuit proof manner and that overloading by other consumers can be
excluded.
Operating Instructions
Motor side
Rated output
voltage
FWP...
[V]
[A]
25A14F 700
25
0 to 480
50A14F 700
50
0 to 480
50A14F 700
50
0 to 480
50A22F 700
50
0 to 480
50A22F 700
50
0 to 480
0 to 480
0 to 480
0 to 480
0 to 480
80A22F 700 2x80 0 to 480
80A22F 700 2x80 0 to 480
Motor side
Rated
output
voltage
FWP...
[V]
[A]
50A22F 700
50
0 to 600
50A22F 700
50
0 to 600
50A22F 700
50
0 to 600
50A22F 700
50
0 to 600
50A22F 700
50
0 to 600
50A22F 700
50
0 to 600
0 to 600
0 to 600
0 to 600
Connecting-up
Cross-
section
current VDE
[V]
[A]
[mm²]
6.1
2.5
8.0
2.5
10.2
2.5
13.2
2.5
17.5
4.5
25.5
10
34.0
10
37.5
16
47.0
25
59.0
25
72.0
35
Cross-
section
current VDE
[V]
[A]
[mm²]
4.5
2.5
6.2
2.5
7.8
2.5
11.0
2.5
15.1
4
22.0
6
29.0
10
34.0
10
46.5
16
1)
AWG
14
14
14
14
12
8
8
6
4
4
2
1)
AWG
14
14
14
14
12
10
8
8
6
7-5