Parameterizing Steps
Reference quantities
Dependent
reference values
Automatic motor
identification
WARNING
9-18
Display of function parameters, monitoring parameters, and connectors
are limited to double the reference value.
After fast parameterization, the reference and rated motor values are
identical. This enables signal representation (e.g. via connectors) up to
twice the rated motor values. If this is not sufficient, you can switch to
the menu "Drive setting" (P060 = 5) to adapt the reference values. The
following parameters are available for that purpose:
P350
Reference current
P351
Reference voltage
P352
Reference frequency
P353
Reference speed
P354
Reference torque
Speed reference frequency and reference speed are always coupled
via the number of pole pairs.
60
=
×
P353
P352
P109
If one of the two parameters is altered, the second is converted using
this equation.
The reference power (in W) is calculated from the reference torque and
reference speed:
×
P354
P353
=
R
W,
ref
60
Power values of the closed-loop control are also stated as a percentage
and refer to the reference power stated. Conversion to rated motor
power is possible using the ratio P
×
×
P113
2
=
P
mot,
rated
60
For exact determination of the motor parameters, it is possible to carry
out automatic motor identification and speed controller optimization.
For this purpose, the procedures of the "Drive setting" have to be
observed. If one of the vector control types (P100 = 3, 4, 5) of a
converter without a sinusoidal output filter and of an induction motor
without an encoder or with a pulse encoder (correct number of pulses in
P151) is used, the motor identification procedure can be shortened. In
this case, "Complete motor identification" has to be selected (P115 = 3)
and the converter has to be powered up accordingly if the alarms A078
and A080 appear.
During motor identification inverter pulses are released and the drive
rotates!
For reasons of safety, identification should first be carried out without
coupling of the load.
in A
in V
in Hz
in rpm
in Nm
×
×
π
2
/ P
W,ref
mot,rated
π
×
P
108
Operating Instructions
04.2006
.
6SE7087-6KD60
Siemens AG
SIMOVERT MASTERDRIVES