Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens simovert masterdrives Betriebsanleitung Seite 345

Vorschau ausblenden Andere Handbücher für simovert masterdrives:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

04.2006
P130 = ?
P130 =
P130 =
P130 =
10,13,14
5
11,12,15,16
P151 = ?
P131 = ?
P139 = ?
P140 = ?
P141 = ?
P100 =
0,1,2
P330 = ?
P339 = ?
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
Select the motor encoder
5: External SBP board
10: Without motor encoder
11: Pulse encoder (default if P095=2, P097>0)
12: Pulse encoder with control track
13: Analog input 1
14: Analog input 2
15: Pulse encoder with zero track
16: Pulse encoder with zero and control track
WARNING
Please check that the encoder has been connected
correctly!
Pulse encoder: Do not mix up tracks A and B!
Analog tachometer: Check voltage polarity (direction of
rotation) and amplitude!
In the event of faults the drive may involuntarily race to
maximum speed! For testing the encoder see parameter
P115=7 and P115=3 and 4.
Enter the pulse number/revolution of the pulse encoder
Select TmpSensor
0: KTY84 (evaluation via P380/P381)
3: PT100 (evaluation only possible for SBP)
Configuration of setpoint encoder
Setpoint encoder pulse number
Reference frequency of setpoint encoder
Characteristic 0: Linear characteristic (constant torque drives)
1: Parabolic characteristic (fans/pumps)
Release the edge modulation systems (FLM)
0:
All systems
1:
Edge modulation systems from 60 Hz
2:
Edge modulation systems from 100 Hz
3:
No edge modulation systems
4:
Overmodulated space vector modulation
Operating Instructions
Parameterizing Steps
9-55

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Vector control

Inhaltsverzeichnis