Terminal strip X9 (only for units with a rated input voltage of
DC 270 - 310 V)
X9 - external
DC 24 V supply,
main contactor
control
1
2
3
4
5
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
All external cables relevant to the safety function are protected, e.g.
installed in cable ducts, to preclude the possibility of short circuits.
Cables must be installed in compliance with the requirements of
EN 60204-1, Section 14.
In the circuit shown in Fig. 7-3, the tumbler does not release the moving
protective device until the drive has stopped. It may be possible to omit
the tumbler if the risk assessment of the machine deems this to be
safe. In this case, the NC contact of the protective device is connected
directly to terminals Y11 and Y12 and electromagnet Y1 is omitted.
Binary input X is negated with signal "OFF3", i.e. at 24 V, the converter
decelerates the motor to zero speed along the parameterized
deceleration ramp. The converter signals zero speed via binary output
Y, thus energizing relay K2.
Once the motor has stopped, the safety relay in the converter is opened
and the coil of main contactor K1 remains at 24 V via the checkback
contact. If contacts in the safety relay are sticking, the checkback
contacts do not close and the safety combination on the right
deenergizes main contactor K1 via delayed contacts 47/48 when the
set delay period expires.
The 5-pole terminal strip is used for connecting up a 24 V voltage
supply and a main or bypass contactor.
The voltage supply is required if the inverter is connected up via a main
or bypass contactor.
The connections for the contactor control are floating.
Terminal
Designation
1
+24 V (in)
2
0 V
3
n.c.
4
Main contactor control
5
Main contactor control
Connectable cross-section: 2.5 mm² (AWG 12)
Table 7-4
Connection of external aux. voltage supply DC24 V and main contactor
control for units for voltage supply DC 270 V to 310 V)
Operating Instructions
Description
24 V voltage supply
Reference potential
Not connected
Main contactor control
Main contactor control
Connecting-up
Range
DC24 V ≥ 2.5 A
0 V
1 kVA
AC 230 V
7-9