Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens simovert masterdrives Betriebsanleitung Seite 353

Vorschau ausblenden Andere Handbücher für simovert masterdrives:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

04.2006
Automatic
parameterization
and motor
identification
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
The following parameters are calculated or set to fixed values during
automatic parameterization (P115 = 1):
P116
P236
P117
P240
P120
P258
P121
P259
P122
P273
P127
P274
P128
P278
P161
P279
P215
P283
P216
P284
P217
P287
P223
P291
P235
P293
♦ P350 to P354 are only set to the rated motor quantities in the
converter status "Drive setting" (P060 = 5) or "Quick
parameterization (P060 = 3).
♦ In converter status "Drive setting" (but not in "Ready" status),
parameters are assigned automatically on selection of standstill
measurement P115 = 2, 3.
♦ During the standstill measurement P115 = 2, 3, the following
parameters are measured or calculated:
• P103, P120, P121, P122, P127, P347, P349.
The controller settings resulting from these values are in: P283,
P284, P315, P316.
♦ During the rotating measurement P115 = 3, 4, P103 and P120 are
adjusted.
♦ During the n/f controller optimization P115 = 5, the parameters
P116, P223, P235, P236, P240 and P471 are determined.
In principle, automatic parameterization (P115 = 1) or motor
identification (P115 = 2, 3) should be carried out as soon as one of the
following parameters are adjusted in the converter status "Drive setting"
(P060 = 5):
P068 = Output filter
P095 = Motor type
P097 = Motor number
P100 = Control type
P101...P109 = Motor rating plate data
P339 = Release of modulation system
P340 = Pulse frequency
P357 = Sampling time
Operating Instructions
P295
P337
P303
P339
P306
P344
P313
P347
P315
P348
P316
P388
P319
P392
P322
P396
P325
P471
P326
P525
P334
P536
P335
P602
P336
P603
Parameterizing Steps