Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection - Maico PPB 30 O Montageanleitung

Endmontage-set
Vorschau ausblenden Andere Handbücher für PPB 30 O:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

8 Installation
PPB 30 K unit #1
PPB 30 K units #2
PPB 30 K units #3
13.Fit electronics compartment cover and screw
down (2 screws).
14.Plug in plugs (8-pin) of both fan connecting
cables directly onto the circuit board. The
plugs are coded and cannot be confused. In-
sert connecting cables in intended slot in the
housing. With PPB 30 K/ PPB 30 RC units,
ensure that the humidity sensor is not
covered.
15.Ensure that the two G3 air filters are correctly
inserted in the holders.
F Front cover
R Locking lever
16.Attach front cover and swivel down until the
front cover engages at the two locking levers.
8.6 230 V electrical connection
• The two internal EC fans of the ventilation unit
are supplied with 12 V DC and activated using
a PWM signal (0 – 5 V).
• The power supply for the ventilation units is
provided by the room air control for up to 6 fans
(up to 3 PPB 30).
• The room air control is supplied with 230 V AC.
• The unit variant PPB 30 RC has a fully integ-
rated control unit with 230 V connection.
Note the following safety instructions.
DANGER Danger of electric shock.
Before installing the electrics, shut down all sup-
ply circuits, switch off mains fuse, secure against
being accidentally switched back on and position
a visible warning sign. During operation, the
board cover and front cover of the internal hous-
ing must be mounted.
WARNING Danger of burns/fire due to
overload caused by incorrect connection or
connecting too many units to a RLS 45 O /
RLS 45 K.
Connect units in accordance with connection dia-
gram. Observe permissible number of ventilation
units per room air control/power unit.
WARNING Danger of electric shock if the
12 V low voltage and 230 V are not disconnec-
ted or are insufficiently disconnected.
Ensure a safety distance between 230 V and 12
V cables. Ensure minimum distance of 8 mm.
WARNING Danger of electric shock if the
connection on the 230 V input of the PP 45 RC
units and the RLS 45 O / RLS 45 K controller
is incorrect.
Ensure a phase balance between all components
connected to the ventilation system.
WARNING Danger of electric shock if the
RLS 45 O / RLS 45 K control is installed within
the protection zone.
No IP protection present (IP 00). The room air
control may only be installed outside protective
zones 0, 1 or 2.
39

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ppb 30 kPpb 30 rcRls 45 oRls 45 k

Inhaltsverzeichnis