9 Commissioning
LEDs
* The service menu items are set according to the 3-digit binary code 111, e.g. the adjuster "5" is dis-
played as 101 → Upper and lower LEDs light up.
Bold
Factory settings
LED flashes quickly
LEDs
44
Parameters
Power units (LTs) or
room air controls (RLS)
Sensors
Parameters
Set value / Bin-
Setting / description
ary display*
0
Operation without further
1
LTs/RLS
2
Operation with 1 LT or RLS
3
Operation with 2 LTs or RLS
4
Operation with 3 LTs or RLS
5
Slave no. 1
6
Slave no. 2
Slave no. 3
Adjuster for adding further room
air controls (RLS) or power
units (LTs) to this room air con-
trol. Example: Two further RLS
(RLS #2 and #3) are connected
to RLS #1.
Set value = 2.
Set set value 4 on RLS #2 and
set value 5 on RLS #3.
Notice: Only single-type RLS
combinations are permitted!
0
No sensor
1
1 internal sensor
2
1 internal sensor +
3
1 external sensor
4
1 internal sensor + 2 external
5
sensors
6
1 internal sensor + 3 external
7
sensors
0 internal sensors + 1 external
sensor
0 internal sensors + 2 external
sensors
0 internal sensors +
3 external sensors
Select how many internal and
external sensors are connec-
ted/combined. The PP 45 HYI
internal sensor and the
PP 45 HY, PP 45 CO2 and
PP 45 VOC external sensors
are available.
LED flashes slowly
Set value / Bin-
Setting / description
ary display*