gb | 8. Electrical connection (specialist installer)
9. Secure external cover to frame with
screw supplied.
7.6 Frame of PP 60 K-SE internal
cover
1. Remove plaster protective cover on
inside if necessary.
2. Check angle of inclination of fitted wall
sleeve. There must be an inclination
of 1...2 % to the outside.
3. Take internal cover [8] off frame of
internal cover [6].
4. Align frame of internal cover [6]
horizontally and centred in the middle
to the wall insulation sleeve [10].
5. Use dowels and screws (6 mm in
diameter, provided by customer) to
secure frame to internal wall.
7.7 PP 60 K-SE ventilation unit
1. Remove plaster protective cover on
inside if necessary.
2. Place G3 external filter [3] (optional
M6) on slide-in module [4] and turn
down pasting lugs. The pasting frame
must be facing the slide-in module.
3. Place G3 internal filter [5] (optional
M6) on slide-in module [4] and turn
down pasting lugs. The pasting frame
must be facing the slide-in module.
4. Slide slide-in module [4] including
filter, heat exchanger and EC fan into
wall insulation sleeve [10]. Consider
the sticker „Unten/Bottom/ Bas". The
heat exchanger must be facing you.
5. Seal ventilation unit with internal
cover [8].
 You will hear it engage.
34
8. Electrical connection
(specialist installer)
Only qualified electricians are permitted
to make the electrical connections, in
compliance with the wiring diagrams
below.
Make sure to observe the relevant
regulations for electrical installation; in
Germany this is particularly VDE 0100
with the corresponding parts.
Check the mains supply to the building
before commissioning. This must comply
with the voltage specified on the mains
adapter (230 V /
50 Hz).
DANGER
Danger to life from electric shock!
Deactivate the fuse in the fuse box and
protect against being accidentally switched
back on. Fit a warning notice on the fuse
box.
8.1 RLS PP-K room air control
The customer should provide control
cables between the room air control and
PushPull 60 K ventilation units, types
J-YSTY and 0.8 mm, 4 wires.
NOTICE
Material damage if the incorrect cables
are used.
Only connect the room air control to
permanently wired electrical installations
with NYM-O or NYM-J, (3 x 1.5 mm²) type
cables. Mains isolation device required
with contact openings of at least 3 mm at
each pole.