Configuration via Explicit Messages (continued)
3.4

Fault State

For each output at the port pins, a safe state can be
pre-defined, which should be adopted in the case of a loss
of bus communication.
The Fault State settings can be implemented via the
following Class Instance Attribute of the Explicit Messages.
Activate / deactivate Fault State
Class
Instance Attribute
9 (0x09)
1 – m
6
1)
m: Number of outputs
1)
Tab. 3-3:
Values for Fault State – Activation/Deactivation
Fault State Action
Class
Instance Attribute
9 (0x09)
1 – m
5
1)
m: Number of outputs
1)
Tab. 3-4:
Values for Fault State – Fault State Action
The Fault State settings are only stored temporarily
in the module. They are deleted again after a
power reset.
In order to ensure a permanent Fault State
configuration, the configuration must be
programmed via the PLC so that it can be
transferred to the module again when the system
is restarted.
Discrete Output Current Value
Class
Instance Attribute
9 (0x09)
1 – m
100
1)
m: Number of outputs
1)
Only for Pin 2
2)
Tab. 3-5:
Values for Discrete Output Current Value
www.balluff.com
Value
0: Fault State
disabled
1: Fault State
enabled
Value
0: Output on
1: Hold last state
Value
1: 1 A
2: 2 A
4: 4 A
2)
english
13