Herunterladen Inhalt Inhalt Diese Seite drucken

Integration; Address Details; Data Configuration; Configuration Data - Balluff BNI EIP-508-105-Z067 Konfigurationsanleitung

Vorschau ausblenden Andere Handbücher für BNI EIP-508-105-Z067:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BNI EIP-508-105-Z067
Network interface
2
System integration (continued)
2.2

Integration

2.2.1

Address details

The following settings are assigned at the factory:
IP address: 192.168.1.1
Subnet mask: 255.255.255.0
Gateway address: 192.168.1.1
2.2.2

Data configuration

Enter the values from Tab. 2-1 in the control system. They
describe the data sizes of the entry, output and

configuration data.

Data size
Instance ID
INPUT
OUTPUT
CONFIG
Tab. 2-1:
Data configuration
2.2.3
Configuration data
Tab. 2-2 shows an assignment of the configuration data
sequence. The stated standard values describe a
configuration with the IO-Link function on Pin 4 and
standard I/O functions on Pin 2 and 4 of every port. The
input and output functions of the configured standard I/O
ports are set using the process data.
Byte
Slot Module
part
0...1
1
Module
2...25
2
IO-Link
Port 0
26...49
3
IO-Link
Port 1
50...73
4
IO-Link
Port 2
74...97
5
IO-Link
Port 3
98...121
6
IO-Link
Port 4
122...145
7
IO-Link
Port 5
146...169
8
IO-Link
Port 6
170...193
9
IO-Link
Port 7
Tab. 2-2:
Configuration data
8
english
Length of data
100
392
101
262
102
194
Description
General configuration for
the overall module
Configuration of the
IO-Link Port 0
Configuration of the
IO-Link Port 1
Configuration of the
IO-Link Port 2
Configuration of the
IO-Link Port 3
Configuration of the
IO-Link Port 4
Configuration of the
IO-Link Port 5
Configuration of the
IO-Link Port 6
Configuration of the
IO-Link Port 7
Module configuration BNI EIP-508-105-Z067
Byte
Bit
7 6 5 4 3 2 1 0
0
P3
P2
P1
1
P7
P6
P5
Tab. 2-3:
Module configuration
IO-Link Port configuration
Byte
Bit
7
6
5 4 3 2 1 0
2
Basis
Time
3
Validation type
4
Manufacturer code 1
5
Manufacturer code 2
6
Device code 1
7
Device code 2
8
Device code 3
9
Serial number 1
...
...
24
Serial number 16
25
Parameter server
...
The data of the other IO-Link Ports are structured
identically and described below.
Tab. 2-4:
IO-Link Port configuration
Description
P0
Port function 0x00:
Standard-I/O 0x01:
P4
IO-Link
Description
Cycle Time
– 0: No validation
– 1: Compatible
(VID + DID)
– 2: Identical
(VID + DID +
SerNum)
Manufacturer
code
Device code
Serial number
– 0x8X Switch on
– 0x0X Switch off
– 0x40 Delete
– 0xX1 Switch on
upload
– 0xX2 Switch on
download

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis