Operating Indicators (Status Led) - IFM Electronic ecomat 100 CR2011 Gerätehandbuch

Ausgangs-modul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

value range
values
value output
free-wheel diode
is integrated!
Operating indicators
LED colour
Status
OFF
ON
green
flashing
2 Hz
OFF
red
ON
yellow OUT
ON
All manuals and user guides at all-guides.com
-2000 ... +2000 mA
> +2000 mA are rounded to +2000 mA
< -2000 mA are rounded to -2000 mA
0 ... +100 mA are rounded to +100 mA,
-100 ... 0 mA are rounded to -100 mA.
100 ... 2000 mA are present at the odd-numbered
outputs (1, 3, 4, 7)
-2000 ... -100 mA are present at the even-numbered
outputs (2, 4, 6, 8)
To avoid a falsification of the measuring result, no external
free-wheel diode must be connected in parallel with the
load in operating mode „current-controlled output".
CANopen state: PREOPERATIONAL / PREPARED
- NodeGuard error (if NodeGuarding is active)
- no synch objects (if synch monitoring is active)
binary output: output is active / ON
analog output: PWM preset value is unequal to 0
preset current value > absolute value 100
Description
no supply voltage
module in the stand-by mode
outputs = OFF
module active
CANopen state: OPERATIONAL
outputs are updated
communication o.k.
communication disturbed
CR2011
OUTPUT MODULE