Herunterladen Inhalt Inhalt Diese Seite drucken

Dimensions; Operating Indicators (Status Leds) - IFM Electronic ecomat100 CR2013 Gerätehandbuch

Ein-/ausgangs-modul
Vorschau ausblenden Andere Handbücher für ecomat100 CR2013:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Dimensions

Operating indicators
LED colour
Status
OFF
ON
green
flashing
2 Hz
OFF
red
ON
yellow IN
ON
ON
yellow OUT
flashing
1 Hz
60
7
8
5
6
PWR
3
4
DIA
1
2
28,5
7,5
39
no supply voltage
module in the stand-by mode
CANopen state: PREOPERATIONAL / PREPARED
outputs = OFF, input states are not transferred
CANopen state: OPERATIONAL
outputs are updated, input states are transferred
communication o.k.
communication disturbed
- NodeGuard error (if NodeGuarding is active)
- no synch objects (if synch monitoring is active)
- CANopen interface fault
binary output: output is active / ON
analog output: PWM preset value is greater than 1%
output driver indicates error:
- short circuit/overload/no load (worst case load current < 900mA)
- too high a temperature/undervoltage/overvoltage
The LED function can be blocked (see page 29, OBD, index 2002).
Input/output module CR2013
M12x1
Description
module active
input is ON
23

Werbung

Kapitel

Inhaltsverzeichnis
loading