Deep Packet Inspection (DPI)
12.1 dpi
[sanity-check]: Sanity check including format and specification.
[reset]: Reset connection message.
[debug]: Debug output in reset message.
[common-addr-size]: Set common address size.
[io-addr-size]: Set IO address size.
[allow-101]: Allow IEC101 type IDs.
Parameter Value
1..32
P-1
string
P-2
readonly
P-3
readwrite
common
any
advanced
1..255
P-4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
30
31
32
33
34
35
36
37
38
39
40
45
46
47
48
49
50
51
58
59
60
61
62
63
64
62
Meaning
Profile index 1 - 32
Profile description/name
Read only type IDs for type ID list.
Read write type IDs for type ID list.
Common type IDs for type ID list.
All possible type IDs for type ID list (allow any type ID).
Lets the user specify customized type IDs for type ID list.
Comma separated type ID e.g 1,2,3.
Single point information m-sp-na-1
Single point information with time tag m-sp-ta-1
Double point information m-dp-na-1
Double point information with time tag m-dp-ta-1
Step position information m-st-na-1
Step position information with time tag m-st-ta-1
Bit string of 32 bit m-bo-na-1
Bit string of 32 bit with time tag m-bo-ta-1
Measured value, normalized value m-me-na-1
Measured value, normalized value with time tag m-me-ta-1
Measured value, scaled value m-me-nb-1
Measured value, scaled value with time tag m-me-tb-1
Measured value, short floating point value m-me-nc-1
Measured value, short floating point value with time tag m-me-tc-1
Integrated totals m-it-na-1
Integrated totals with time tag m-it-ta-1
Event of protection equipment with time tag m-ep-ta-1
Packed start events of protection equipment with time tag m-ep-tb-1
Packed output circuit information of protection equipment with time tag m-ep-
tc-1
Packed single-point information with status change detection m-ps-na-1
Measured value, normalized value without quality descriptor m-me-nd-1
Single point information with time tag cp56time2a m-sp-tb-1
Double point information with time tag cp56time2a m-dp-tb-1
Step position information with time tag cp56time2a m-st-tb-1
Bit string of 32 bit with time tag cp56time2a m-bo-tb-1
Measured value, normalized value with time tag cp56time2a m-me-td-1
Measured value, scaled value with time tag cp56time2a m-me-te-1
Measured value, short floating point value with time tag cp56time2a m-me-tf-1
Integrated totals with time tag cp56time2a m-it-tb-1
Event of protection equipment with time tag cp56time2a m-ep-td-1
Packed start events of protection equipment with time tag cp56time2a m-ep-te-1
Packed output circuit information of protection equipment with time tag
cp56time2a m-ep-tf-1
Single command c-sc-na-1
Double command c-dc-na-1
Regulating step command c-rc-na-1
Setpoint command, normalized value c-se-na-1
Setpoint command, scaled value c-se-nb-1
Setpoint command, short floating point value c-se-nc-1
Bit string 32 bit c-bo-na-1
Single command with time tag cp56time2a c-sc-ta-1
Double command with time tag cp56time2a c-dc-ta-1
Regulating step command with time tag cp56time2a c-rc-ta-1
Setpoint command, normalized value with time tag cp56time2a c-se-ta-1
Setpoint command, scaled value with time tag cp56time2a c-se-tb-1
Setpoint command, short floating point value with time tag cp56time2a c-se-tc-1
Bit string 32 bit with time tag cp56time2a c-bo-ta-1