If the switch is set to "ON", the bus address of the measuring device whose values are to be
displayed can be set using DIP switches 1 to 64.
Valid address range: 0 to 125
3.
"Set" DIP switch set from "OFF" to "ON"
Switch which is used to accept the offset setting in the device.
The settings are only accepted if the "Set" switch is changed from "OFF" to "ON". If the "Set"
switch is set to "ON", device power-on does not have any effect, nor does a change in the
"Set" switch setting from "OFF" to "ON" if the write lock is enabled.
If all the DIP switches are set for the address, address 127 can be configured. This
deletes the settings for the channel. A channel that was previously configured can be
disabled again in this way.
Address 126 is not valid for the necessary Data Exchange Telegram. The device displays
a configuration error with this address.

6.4.4 Configuring an offset

Using the DIP switch, it is possible to set the index (offset) of the first byte of the value to be
displayed in relation to the set bus address of the data source.
An index (offset) of between 0 and 127 can be set via the DIP switches.
The setting is made as follows:
1.
"AI1/AI2" DIP switch
This DIP switch is used to select whether the configured index (offset) refers to analog
input 1 (switch set to "ON") or analog input 2 (switch set to "OFF").
2.
"Address/Offset" DIP switch set to "OFF"
If the switch is in the "OFF" position, an index (offset) can be set for analog input 1 or analog
input 2.
3.
"Set" DIP switch set from "OFF" to "ON"
Switch which is used to accept the offset setting in the device.
The settings are only accepted if the "Set" switch is changed from "OFF" to "ON". If the "Set"
switch is set to "ON", device power-on does not have any effect, nor does a change in the
"Set" switch setting from "OFF" to "ON" if the write lock is enabled.
Endress+Hauser
Operating the field indicator
43