Installation
Operating temperature range:
-40 to +80 °C (-40 to +176 °F)
NOTICE
Shorter display operating life at higher temperatures
Where possible do not operate the device in the higher temperature range.
The display can react slowly at temperatures < -20 °C (-4 °F).
The readability of the display is no longer guaranteed at temperatures < -30 °C (-22 °F).
4.2.1 Dimensions
Abb. 2: Dimensions of the field indicator; dimensions in mm (in)

4.2.2 Mounting location

Information about the conditions (such as the ambient temperature, degree of protection, cli-
mate class etc.) that must be present at the installation point so that the device can be mounted
correctly, is provided in the "Technical data" section in the Operating Instructions provided.
4.3

Installation instructions

The device can be mounted directly on the wall or the optional mounting bracket can be used for
wall and pipe mounting ( å 3).
4.3.1 Mounting directly on the wall
Proceed as follows to mount the device directly on the wall:
1.
Drill 4 holes
2.
Fit the device on the wall with 4 screws (5 mm (0.2 in)).
4.3.2 Pipe mounting
The mounting bracket is suitable for pipes with a diameter between 1" - 5". The mounting kit
consists of a mounting plate (item 1), 2 clamps (item 2) and 4 screws (item 3).