0x40 and below 0x80), the ' U ncertain measured value status' symbol is lit. If the status is ' b ad'
(quality code below 0x40), within the 7-segment area the display will show "BAD-" and the
channel number where the bad value is published. The entered text continues to be displayed in
the 14-segment area and the bar graph is not shown.
6.3
Configuration via interface & PC configuration software
WARNING
!
The device is not explosion-protected when the housing is open
The device must be configured outside the hazardous area.
To configure the device via the FieldCare Device Setup or DeviceCare software, connect the
device to your PC. For this you will require a special interface adapter, the Commubox FXA291
(see ' A ccessories' section in the Operating Instructions provided).
The four-pin plug of the interface cable must be inserted into the corresponding socket in the
device. The USB plug must be inserted into a free USB port on the PC.
More information on configuring via the PC configuration software can be found in the Operat-
ing Instructions provided.
No power should be supplied via the bus if configuring the PROFIBUS PA indicator with
the DTM via the CDI interface!
To ensure a connection to the device can be established, operation must be set to
"Remote" at the DIP switches. Furthermore write protection, which can be enabled and
disabled via the DIP switches, must be disabled so that the parameters of the field indi-
cator can be modified via the DTM.
The DIP switches are described in the "Operation" section ( ä 39).
6.4

Hardware settings

Hardware write protection can be enabled and disabled via DIP switches inside the field indica-
tor. When write protection is active, parameters cannot be modified. The current write protec-
tion status is displayed in the WRITE_LOCK parameter (Resource Block, see Section 11).
ESD - electrostatic discharge
Protect the terminals from electrostatic discharge. Failure to observe this may result in destruc-
tion or malfunction of parts of the electronics.
To set the DIP switches, proceed as follows:
1.
Remove the housing cover to open the housing.
2.
Configure the DIP switches. Switch to ON = function enabled, switch to OFF = function dis-
abled.
3.
Close the housing cover and secure it.