a) Lead in the power supply cable (Fig. 9/11) through the cable fitting (Fig. 9/M40) in the frequency conver-
ter (Fig. 9/9).
NOTICE
b) Connect the lines with the terminal clamps (Fig. 9/13) as follows:
3~ 400 V terminal designation (Fig. 9/X1)
Terminal no.
1
2
3
4
The cross section of the power supply line must be dimensioned depending on the type of laying and
the max. permissible current. The user must provide for the protection of the power supply line.
Connection data:
Input voltage
Mains frequency
Mains current
Mains fuse
c) Closing of cover:
Place the cover (Fig. 10/8) on the housing of the frequency converter (Fig. 10/9).
Tighten the four screws (Fig. 10/7). Torque 4 Nm (2.95 ft lbs).
Fig. 10 Close the frequency converter
Prematic AG, Märwilerstrasse 43, 9556 Affeltrangen www.prematic.ch
Property damage!
Crushing, buckling or too high tension load can damage the cable.
Ø The cable fitting is used as strain relief; the PE connecting cable must be
leading (clearly longer)!
Designation
L1
L2
L3
PE
Value
400 V-15 % – 480 V+10 %
47 – 63 Hz
39.9 A
63 A
Assignment
Net phase 1
Net phase 2
Net phase 3
Protective earth conductor