the equipment must be installed in a correct and workmanlike manner in compliance with all pertinent standards;
-
after installation, the machine owner must be given the "declaration of conformity".
This product may only be installed and serviced by qualified personnel in compliance with current laws, regulations
and directives.
When designing its products, TAU observes all applicable standards (please see the attached declaration of conformity)
but it is of paramount importance that installers continue to strictly observe the same standards when installing the
system.
Unqualified personnel or those who are unaware of the standards applicable to the "automatic gates and doors"
category may not install systems under any circumstances.
Whoever ignores such standards shill be held responsible for any damage caused by the system!
Do not install the unit before you have read all instructions.
CONTROL PANEL FOR 230 V AC SINGLE-PHASE MOTOR
MICROPROCESSOR-CONTROLLED LOGIC
LINE INPUT FUSE
433.92 MHz BUILT-IN RADIO RECEIVER
ELECTRONIC TORQUE LIMITING DEVICE
INSTALLATION
ATTENTION:
-
do not use single cables (with one single wire), ex. telephone cables, in order to avoid breakdowns
of the line and false contacts;
-
do not re-use old pre-existing cables.
This product must be correctly installed by a qualified fitter. The maker declines all liability for damage
caused by incapacity or neglect.
In particular:
1. position the board vertically and as near as possible to the gear motor, taking care to keep the
connection cables as short as possible. When the control circuits comprise very long lines (over 50 m) it
should be decoupled with relays installed in the control panel;
2. make sure the cross-section of the power cables (power input, motors, earth and flashing light) is at
least 1.5 mm² and, in any case, sufficient for the absorption and length of the wires. The above also
applies to the other cables used by control and auxiliary devices except that the minimum cross-section
is reduced to 0.5 mm²;
3. make connections to the terminal board so as not to alter the level of protection offered by the
container which must be installed in a dry and protected place;
4. keep the power circuits separate from the control and auxiliary circuits, especially if the cables are long;
5. short any unused Normally Closed contacts.
NB: the product must be properly earthed and the safety regulations in force in the country of
installation must be observed.

TECHNICAL CHARACTERISTICS

Power input to board
Maximum power output
Primary power input line rapid fuse
Logic circuit input voltage
Working temperature
Box protected to
TERMINAL BOARD CONNECTIONS
1 - 2
POWER input 230Vac, 50 Hz, single-phase;
3 - 4 - 5 MOTOR POWER output 230Vac, 50Hz, single-phase;
1 - 5
flashing light power output. The signal is not modulated and therefore a board with a built-
in flashing function must be used;
6 - 8
OPEN LIMIT SWITCH input (normally closed contact), common=8. If the motor has internal limit
switches is enough to make a bridge between the contact;
230V AC - 50Hz
600W
250V AC-F6,3A
5V DC
0°C ÷ + 70°C
IP43
6