CONTROL BOARD FOR T-ONE3B GEARMOTOR
•
MICROPROCESSOR-CONTROLLED LOGIC
•
INPUT STATUS LED'S
•
LINE INPUT FUSE
•
"PEDESTRIAN GATE" FUNCTION
•
BUILT-IN FLASHING LIGHT CIRCUIT
•
433.92 MHz 2 CHANNEL BUILT-IN RADIO RECEIVER (CH)
•
BATTERY CONNECTOR
•
ENCODER SENSOR FOR OBSTACLE DETECTION AND SELF-LEARNING OF TRAVEL
•
ADJUSTABLE DECELERATION
•
DIAGNOSTICS OF MALFUNCTIONS SIGNALLED BY LED
•
EN COMPLIANT AND CERTIFIABLE UP TO 300 KG LEAF
ATTENTION:
-
do not use single cables (with one single wire), ex. telephone cables, in order to avoid
breakdowns of the line and false contacts;
-
do not re-use old pre-existing cables.
TESTING
When you have completed the connection:
•
All the green LEDs must be on (each of them corresponds to a Normally Closed input). The go off
only when the controls to which they are associated are operated.
•
All the red LEDs must be off (each of them corresponds to a Normally Open input). The light up
only when the controls to which they are associated are operated. Except for the DL3 diagnostics
led which must always be on.
TECHNICAL CHARACTERISTICS
Board power supply
Max motor power DC
Fast acting fuse for protection of input power supply 13.5 V AC (F1 - 5x20)
Fast acting fuse for motor protection (F2 - 5x20)
Fast acting fuse for protection of auxiliary circuits 24 V DC (F3 - 5x20)
Motor power supply circuits voltage
Auxiliary device circuits supply voltage
Logic circuits supply voltages
Operating temperature
Box protected to
CONNECTIONS TO TERMINAL BOARD
Terminals
Function
POWER
FS1 - FS2
SUPPLY
FIXED SAFETY
1 - 3
Description
board supply input 18,5 V AC – Powered by the toroidal trans-
former housed in the T-ONE3B motor and protected by a fuse
on the 230 V AC power supply.
SENSITIVE EDGE input (resistive sensitive edge or fixed safety
edge); Works only when the gate is opening; temporarily stops
the gate and partially closes it by about 20 cm in order to allow
the obstacle to be removed.
1= SENSITIVE EDGE, 3= COMMON.
EDGE
Note: if a resistive sensitive edge is connected, set dip-
switch no. 9 to ON;
If a fixed safety edge with NC contact is connected, set dip-
switch no. 9 to OFF.
K120M
18,5 V AC - 50 Hz
50 W - 24 V DC
F 16 A
F 10 A
F 2 A
24 V DC
24 V DC
5 V DC
-20 °C ÷ +70 °C
IP 44